three phase 180kva diesel generator can take how much load
in amp and what is formula to get this?
Answer Posted / elangkumanan
kva =kva*1000
-----------
1.732*v*i*cos0
180*1000
= --------
1.732*440*i*0.85
I =180000
--------=278 A
647.768
| Is This Answer Correct ? | 4 Yes | 5 No |
Post New Answer View All Answers
State thevenintheorem?
Can Anyone suggest the Standards (IEC or IS) for selecting copper current density?
what is the interrelation between voltage current torgue speed and magnetic flux in case of different types of electric motors
What is the tests required for a 132 kV, 400 kV , 765 kV for a Circuit Breaker and Power Transformer before commissioning ?
what is droop control?
What is Faraday's law
what is data block in plc ? How the values of data block are written and read by hmi ? what is the difference between function and function block ?
Dear sir, I completed DECE In the year 1995.Now i am working in a private company from last 10 years as an Electrical supervisor.The company having a 1000 KVA transformer.Now i try to apply "C" Licence. I am eligible or not.If not eligible,pls give solution.
what is self capacitance of inductor
what is earth-fault?when it occurs? to check where it occurs what type of test should we do?
What is difference between slip rings and carbon burushes?
hi friends this is a newcomer in your community of enthusiastic peoples. i am preparing for SSC (CPWD JUNIOE ENGG EXAM FOR ELECTRICAL) pls guide me on the same how to crack it? PLS LET ME KNOW IS ANYONE THERE WHO PASED IT? CAN I GET THE QUESTION PAPERS OF PREVIOUS EXAMINATIONS?
Can anybody inform me about the pattern of ECIL GET( Graduate Engineers Trainee) interview for Electrical students? Will there be HR round as well? I thought of preparing for 2 to 3 subjects thoroughly. Will it be sufficient? Please share your thoughts.
how to find 5 kilo meter long under ground 33 kv cable fault location if IR VALUE shows 0.05 M ohm @5000 volt.and cable fault locator shows some time fault distance 3 kilo meter ,3.7 kilo meter and some time 1 kilo meter? now how to find the fault location that where is leakage. note--it is tested with 5000 kv megger and insulation resistance is 0.05 M ohm. and some time 0.03 M ohm comes.
What is the maximum breakdown voltage of 11KVA and 66 KVA power line and how it is calculated?