after parallaing two generators current is shooting up in
both the generators.for ex: load is 400 kw..after paralling
and load sharing current in running gen is approx 900 amps
and incoming is 750 amps which is too high when trying
toshift the load current in incoming gen is coming more
than 1300 amps and both getting tripped and making
blackout..
Answer Posted / yuvi
This means that the phase angle of the existing generator
and the new incomming generator are not matching. You can
try the bright lamp or the dark lamp method to synk them.
There is no way in which you can directly plug in a
alternator to an active AC system.
| Is This Answer Correct ? | 1 Yes | 1 No |
Post New Answer View All Answers
WHY EARTHING NOT NEEDED IN BATTERY IN SUBSTATION
how oltc works in rectiformers of higher rating (27 mva,200v dc,120kamps) please provide me full information with diaggram.
current transformer balance the power level on both sides. e.g in case of step up, at secondary side voltage rise but current decrease and vice versa in case of step down transformer. but how this power level remains same in case of current transformer and voltage transformer
we have 15 ampere variyac but we want 30 ampere variyac what we do
how u measure/calculate renge of capacitor,capacitor has no any rating tag.what is the theory of measure of capacitons.
Explain RLC circuit?
What is meant by celling voltage & current in excitor ?
What is the drawback of class b amplifier?
why any centrifugal blower draw more current in starting. consider id fan and fd fan?
In three pin plug 6 amp. 220V ac rating. Why earth pin diameter is higher than other two pin? What its purpose ?
why starting current is high and resistance is almost 0 during the starting of motor dc motor...?
3phase motor can be used as a Prime mover for alternator.
what is the saturation point of crgo lamination.
How many methods use the load flow solution?
How it can worked plc based electrical system And which type of software using.