How can we calculate the current if we have load in KVA and if
the load in KW then what formula will be use for calculating
the current. please give both the formula for calculating the
current.
Answer Posted / soumen das biswas
For KVA rating,
The formula for determine the current is:
I = KVA/(1.732 x Voltage) (For three phase system)
I = KVA/Voltage (For Single Phase)
For KW rating
The Formula for current is
I= KW/(1.732 x Voltage x Power factor)(for three phase system)
I = KW/(Voltage X Power factor)(For Single Phase)
| Is This Answer Correct ? | 20 Yes | 2 No |
Post New Answer View All Answers
The 3 phase Delta connection RB=440V, BY=350V,.......* is Line to Line voltage RY= ? And Formula....?
State kirchoff voltage law?
Why have to use copper cable for local isolator to motor ?
why moisture formation found in XLPE Armoured cable outer sheath
How to work meggar?
How to calculate earth fault current for 6.6 KV , 50 HZ , 756 Amps , 3000 RPM , 0.8 PF generator
Can anyone please provide me details of MCCB/Contactor/SFU rating calculations for a motor feeder..for example 50 kw.. not from type-2 cordination chart. i want manual calculations..
Define active and passive network?
Why we make earth connection with Transformer Body and What will be the minimum size of copper wire as per code with respect to KVA rating of Transformer?
There are different classes of protections in power plants.class a,b,c are clear..is there any class d and e r there..and elaborate class b protection.
Will an earth leakage trip be activated if the component or wiring is faulty on low voltage equipment.Example An electrical Cat Scarer placed in the garden and water gets into the wiring.
Thermal withstand capability under full short circuit conditions, in terms of number of times of occurrence of short circuit and corresponding anticipated percentage reduction in transformer life.
The moisture in air will condense at
working of diesel generator ?
What is mathematical model of a control system?