How can we calculate the current if we have load in KVA and if
the load in KW then what formula will be use for calculating
the current. please give both the formula for calculating the
current.
Answer Posted / soumen das biswas
For KVA rating,
The formula for determine the current is:
I = KVA/(1.732 x Voltage) (For three phase system)
I = KVA/Voltage (For Single Phase)
For KW rating
The Formula for current is
I= KW/(1.732 x Voltage x Power factor)(for three phase system)
I = KW/(Voltage X Power factor)(For Single Phase)
| Is This Answer Correct ? | 20 Yes | 2 No |
Post New Answer View All Answers
how to select automotive wire by mathematical equation with given current, vlotage and resistance
What type of a DC motor would you use for a lift?
What is stacking factor? What is its approximate value?
how can we understand that where we have to use ac or dc coil for solenoid valve and why?what is the different between coil of ac and dc explain please.
Leakage current,un balance current which relay using for high voltage transmission?
Why CBCT rating is 50/1A
in 1-phase 230v,how in 3-phase 440v. in each phase in between 230v.
why induction motors are rated at 0.8 power factor.
why it is so called as xlpe(cross linked poly ethyline) cable?
PLZ EXPLIN ABOUT CLASS PS CLASS CT .WHY THEY R DESINED AND FOR WHAT PURPOSE?WHY OTHER CT CANT BE USED AS PS CLASS CT? EXPLAIN IN SIMPLE LAUNGAGE IF POSSIBLE PLZ GIVE CIRCIT DIAGRAM?EMAIL-RAJ_SINGH_0376@SIFY.COM
PLEASE TELL ME ABOUT QUESTION PAPER OF UPCL ENTERENCE EXAM.
sir am giving jspl exam on 19th oct . i belong to eee, so plz send previous question papers ..........to dis id abhilash203@gmail.com
What is the meaning of 40X8X2 busbar dimensions for carring load of 400 Amps
what is meant by LCR meter? where its useful ?
What are the Formula of computing Back up Time of 500kVA UPS with 4 Battery Banks, each bank composed of 43 pcs of Batteries 12V150Ah. How to compute the Back up Time of UPS? We have also 3X500kVA UPS running in Parallel same composition as I write above.