Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How can we calculate the current if we have load in KVA and if
the load in KW then what formula will be use for calculating
the current. please give both the formula for calculating the
current.

Answer Posted / soumen das biswas

For KVA rating,
The formula for determine the current is:

I = KVA/(1.732 x Voltage) (For three phase system)
I = KVA/Voltage (For Single Phase)

For KW rating
The Formula for current is

I= KW/(1.732 x Voltage x Power factor)(for three phase system)
I = KW/(Voltage X Power factor)(For Single Phase)

Is This Answer Correct ?    20 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

The 3 phase Delta connection RB=440V, BY=350V,.......* is Line to Line voltage RY= ? And Formula....?

1653


State kirchoff voltage law?

1076


Why have to use copper cable for local isolator to motor ?

2038


why moisture formation found in XLPE Armoured cable outer sheath

1749


How to work meggar?

1767


How to calculate earth fault current for 6.6 KV , 50 HZ , 756 Amps , 3000 RPM , 0.8 PF generator

1985


Can anyone please provide me details of MCCB/Contactor/SFU rating calculations for a motor feeder..for example 50 kw.. not from type-2 cordination chart. i want manual calculations..

2532


Define active and passive network?

1078


Why we make earth connection with Transformer Body and What will be the minimum size of copper wire as per code with respect to KVA rating of Transformer?

1778


There are different classes of protections in power plants.class a,b,c are clear..is there any class d and e r there..and elaborate class b protection.

2040


Will an earth leakage trip be activated if the component or wiring is faulty on low voltage equipment.Example An electrical Cat Scarer placed in the garden and water gets into the wiring.

1801


Thermal withstand capability under full short circuit conditions, in terms of number of times of occurrence of short circuit and corresponding anticipated percentage reduction in transformer life.

2386


The moisture in air will condense at

1108


working of diesel generator ?

1786


What is mathematical model of a control system?

1082