Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How can we calculate the current if we have load in KVA and if
the load in KW then what formula will be use for calculating
the current. please give both the formula for calculating the
current.

Answer Posted / denzel101

For KVA rating, the formuler for current will be:

I = KVA/(0.707 x Voltage) for three phase system

For KW rating

I= KW/(0.707 x Voltage x cos phi)
for three phase system

Is This Answer Correct ?    5 Yes 17 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

why sometime we get electrical shock while touching the ballon of dish tv connection ? which we should not get.

1991


How to justify this statement ??? "Capacitors in series provide less capacitance but higher voltage breakdown rating for the combination"

1878


if we have a industrial load of 400 kilowatts with 415 volt AC then how much total harmonic distortion (thd%) should be acceptable for steady power system.

1984


What is the practical way to calculate the cable size for known ampere load?

1441


What are conduct on the testing in cf in ur site?

1671


What is the difference between electronic regulator and ordinary rheostat regulator for fans?

1034


How many size of cable required for a 300m long and 30kw inductive lode

1312


How to use earthing on shipments.

1446


with out colour codeing on conductor how can be find what is r,what is b,what is y phases.....

1959


Is there any specialised book to refer about fault level calculation both in MV and LV side??

2076


Define branch?

1097


Hi everyone. Some Generators uses 3-Pole breakers with extra contactors for Neutral. Some uses 4-Pole. Why so? What is the idea behind this? Thanks in advance for the solution. Kr.

2083


In EDO ACBs what is a purpose of closing coil and motor, what is the operation of these devices are they inetconnected. means if we give supply to motor and by BCS we charge Closing coil,what exact is operation is and how it charge a spring of ACB. Sir if anybody has an wiring diagram please send me the link to operate and EDO breaker.

2168


What is meant by reverse polarity and how it can be fixed?

1270


why the active power flow of some line is increased when the active power of out is cut ?

2052