for 12KW motor which cable size has to select for ex.10
meter.
Answer Posted / phanendra babu
the selected cable should have the capability of
withstanding the over load /short ckt currents upto before
operating the protecting device. so assume 0.81 p.f,the load
current is given by apprx 20A .very safe working of copper
cable is 4A to 6A per 1sqmm ,so the size of the cable
suitable for 12kw motor is 6sqmm. copper cable or 16 sqmm
aluminum cable.
the above calculation is for lo current ratings if current
rating increases capacity will decrease.
| Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
What does the a,b,c of 95a,95b,95c relays denotes?
what is the grounding Calculation formula? spouse i want to provide grounding to 3phase 18kw motor or i want to provide ground to 3phase 10kva dry type transformere or you give me any exemple...... Thanks.
Could u pls tell me the NPCIL electrical engineering interview questions for Executive trainee, and also guide me how to face the interview.
kindly send me 11KV MV motor differential protection procedure by primary injection method.
Ceiling Fan and Storage type water heater. Discuss
Why we use auxillary relay ? what is function of differential relay, directional o/c relay?
Z transform is use when system is not a) converges b) diverges
what will happen if OLR CT in all phases are short circuted
volts=230 c=10mf a=??
why starting current is high and resistance is almost 0 during the starting of motor dc motor...?
how oltc works in rectiformers of higher rating (27 mva,200v dc,120kamps) please provide me full information with diaggram.
explain the Trip supervision circuit
What is the previous name of Cox's Bazar
What is marx circuit?
when ac current flows thru d coil of a contactr,it energizes,magnetic field attracts d contact of the coil...nw wont dt ac current in d contct induce current back on to d coil thru mutual inductance leading to high currnt in d coil