for 12KW motor which cable size has to select for ex.10
meter.
Answer Posted / phanendra babu
the selected cable should have the capability of
withstanding the over load /short ckt currents upto before
operating the protecting device. so assume 0.81 p.f,the load
current is given by apprx 20A .very safe working of copper
cable is 4A to 6A per 1sqmm ,so the size of the cable
suitable for 12kw motor is 6sqmm. copper cable or 16 sqmm
aluminum cable.
the above calculation is for lo current ratings if current
rating increases capacity will decrease.
| Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
i have done diploma and btech in EE and live in Chandigarh so kindly help me how can i make my competency certificate in my area.
WHERE NEUTRAL WIRE IS CONNECTED AT DOMESTIC TO TRANSMISSION LINE(SINGLE PHASE TO THREE PHASE)
If SFU is Switch Fuse Unit, What is the expansion for FSHF in Electrical Engineering?
What is mean by Sensitive Earth fault & what are the effects
What is meant by Low Resistance Cable and High Resistance Cable.
how to select fuse rating for a 3-phase motor ???
why the colour of insultor stack , petticoat is brown. Is it has some technical reason.
how to read idmt curva
What is the equivalent circuit of a transformer and its vector diagram?
What is pole of the system?
How relay works, reverse relay, master relay, os relay, earth fault relay and what is its setting point
What is the difference between a fuse and a breaker?
Which motor connection is preferable star-delta or delta-star?
If only R Phase is connected in 2 pole elcb, n is not connected than it will work or not in ground fault.
What is A check, B check, C Check & D check for a diesel Generat