Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

For polarity test on a 11/3.3kV 2.5MVA delta-star Unit
Auxiliary transformer,415V 3-phase supply was applied at
the HV. Connection between Aa was made with a 2.5mm cable.
As soon as power was switched on the cable caught fire and
burnt. This test was then abandoned. It is noteworthy to
say that a similar cable was also used in a similar
transformer for the same. The cable did not burn and test
was successfully completed with good result. What is wrong?
Please, help me out.

Answer Posted / engr. l. o. osuji

Thanks to the respondent.I would like to tell him that no
load was connected besides linking Aa in accordance with
the method for the test. Also, note that similar 2.5mm2
cable has been used on a similar Unit Auxiliary 2.5MVA
11/3.3kV delta-star T/F and 60MVA 132/11kV star-delta T/F
respectively. No burning occurred. Test results were
satisfactory. This piece of information should guide any
contributor. Thanks.

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

why i can not use thimble on capacitor duty contactor

1304


how to calculate slip ring induction motor stator and rotor currents??

2208


HOW TO CALCULATE S/C,O/C,E/F OF ACB.

2528


What are the criteria shall be considers for sizing Fuse and MCB? If the rated current is 10Amps what should be the fuse size / MCB Size?

1564


Dear all, I just want to ask an expert on this forum for some insights. For the magnetic balance test, when applied voltage on a Delta-Star transformer e.g. Dyn11, the following relationships apply for HV side: 1.  H1-H2 = H2-H3 H3-H1 2.  H2-H3 = H3-H1 H1-H2 3.  H3-H1 = H1-H2 H2-H3 For the LV side also: 4.  X1-X0 = X2-X0 X3-X0 5.  X2-X0 = X3-X0 X1-X0 6.  X3-X0 = X1-X0 X2-X0 Is there a similar pattern for Y-d, Y-Y, D-d? And how about Y-z, D-z, Z-y transformers? I've tested a YNzn5 transformer and for LV side I don't see the pattern. In this particular case I got for LV side the following (see values below): H1-H0  H2-H0  H3-H0    X0-X1  X0-X2  X0-X3 128.0  119.9  7.2      29.2   13.3   15.8 70.7   128.4  59.2     23.4   22.0   3.6 7.2    120.1  128.1    13.4   29.3   15.8 What is the relationship here for LV? For row 1 I see the relationship, for row 3 I also see but it's shifted, but for row 2 I don't see such relationship. Any suggestions, answers, someone?

1807


I have done my m.tech in electrical engg discipline. Can any one please suggest me how should I prepare for getting into phd in iit or nit.How should I prepare for getting into lecturership

1638


pls,send the previous year written test questions.

1876


What is step signal?

992


Where servomechanism is used?

1038


What id difference between power and energy?

1255


What if the difference beween internal and exrteranal LBB?

1614


why only exciting current is shown not primary current in transformer???

1805


what you have to see after one week or month from the day of installation of transformer ?

1659


What information we need to prepare relay coordination chart

2265


How is the speed of a DC shunt motor related to the armature current?

1129