Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what happen if i connect DYn11 and DYn1 vector group
transformer in parrallel?other things are same like votage
ration,x/r ratiob etc...

Answer Posted / salah

Dyn11-secondary voltage lags primary by 30degree

Dyn1-secondary voltage leads primary by 30deg

hence it is not satisfying the condition for
pare;;alisation .

if we connect two TR in parallel current drwn form the
source by both transformer is not in phase hence
circulating current will produce & damage the winding as
well in secondary aslo

Is This Answer Correct ?    38 Yes 13 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Why High voltage are generate noise ?

1435


operation of protection relay watchdog contact?

2330


how to select overload-relay for perticular motor 1.for D.O.L. starter 2. for Star-delta starter ????

2781


working function importance of mdc meter

2111


if sf6 gas low in gis what will happen

764


what are inductive and capacitive voltage transformers.what are their applications

1894


What is the resonant peak?

1119


how to enter inverter parameter? without manaual?

1974


what are the major & minor faults that occur in an inverter and in UPS ? And how to repair and resolve them ?

2281


How to calculate impedance volt in Transformer?

2038


Why do we need a separate control desk & PLC control panel in Boiler plant or coal handling plant? Can we provide cost effective Control desk cum PLC panel. Is there is an specific need for control desk.. kindly advice.

2306


Why we use Electrical energy rather than any other type of energy, mostly? Explain behavior of open secondary CT and short circuited secondary PT in energized condition?

1816


What is the loss of transformer of 220kv/11kv, 63/80 MVA and 18.05% impedance

1939


WHAT IS THE CURRENT CARRYING CAPACITY OF 2.5/3 CORE HI TUFF CABLE,WILL IT SAFLEY CARRY 8.6 AMPS OVER 120 METRES,CAN YOU ALSO ANSWER WITH FORMULA FOR WORKINGS OUT ,THANK YOU 3RDYR APPRENTICE.

3509


Salient pole alternator is more stable, why?

2640