We have a bank capacitor rating of 60 KVAR for a overall
load of 160 KVA and we have connected three loads of 50KVA
each. We would like to auto matically correct PF using APFC.
How do we design it?
Answer Posted / rachuri_sree
APFC panel should be connected to main incoming busbar i.e.
from where 160 kva load was fed. 60 kvar capacitors should
be devided into smaller capacities i.e you have to use
either 6x10 kvar or 4x 15kvar or 10x6kvar. I will consider
6x10 kvar. in APFC you have to programe each stage
capacity. here the value is 10 kavar. You have to take 6
no. of capcitor switching duty contactros and to be wired
as per the APFC. It also requires one CT signal and voltage
signal(any one of the three phases of main busbar). You can
program s/on and s/off time in APFC. and also you can
program target power factor. EPCOS apfc is the best
controller I have used.
| Is This Answer Correct ? | 8 Yes | 0 No |
Post New Answer View All Answers
How short circuit MVA(Fault MVA) in a power system calculated for calculating number of earth plates ?
What is 100% protection of generator? Why 100% is not used but 95% is generally used?
Can you explain about pole discrepancy scheme
Why are short circuit ratings always 16kA,25kA,36kA and 50kA.Who has fixed these?
Briefly describe your ideal job?
In vapour absorption refrigeration machine fluids used are
I want to ask that is there any relation between current denesity of copper and material purity. also is ther any standard which defines the standard current denesity of material.
what is the pulse and audio frequency transformer? what is different between induction regulators and tap changing transformer?
how to find out 3 phase complex power in per unit in unbalanced system?
Compare jfet’s and mosfet’s.
What will happen if i replace a inductive proximity switch with photo sensor in a machine?
how i calculate the syncrones generator NGR resistance .if we have a 6mw generator line voltage of generator 11kv also line current 393.3 ampere.
I am apply the AAI. So i want electrical sample question paper in technical with answer my id is vijayjobsmart@gmail.com
Why do we mostly prefer to generate and distribute electricity in 3 phase and not in 4 phase or 5 phase?
power transmission pole used one support , that only for support or earthing