Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Can I use measuring current transformers in protection
purposes?

Answer Posted / ramesh kumar k

Mr.Mohit & Ms. Minnu...

both of u be cool specially... it is not a war field
yaar... ha.. ha...

What ms.minnu said is correct...

u cant use the measuring CT for protection purpose...and
protection ct also can't be used for measuring purpose...
it is not safe...

So Mr. Mohit, from my point of view what you have might
done is.. u have used a CT which u have purchased for
measuring purpose, but still having a additional core for
protection and u might have shorted the metering core
terminals and used the protection core only.. if you have
not used so... I think your system is still safe because
there is not shortcircuit fault tilltime... its very
dangerous if any short circuit occurs... because a metering
CT core is designed in such a way that if there is any
shortcircuit.. it gets saturated and doesnot deliver any
output... if u use this for protection purpose your relay
will not get current(i.e. it gets 0 A which is nothing but
no load condition..). But your relay is set to operate only
in over current conditions... so now what happend.. even in
over current condition, your relay is not getting over
currents hence it will not send any signal to the circuit
breaker...

I suggest, in this regards, u please consult ur higher
authorities...

Ms. minnu, i think we have not studied enough on CTs & PTs
n our basic engineering study...

P.S:
I welcome u both for further clarifications, mail me at
rammy_233@yahoo.com

Is This Answer Correct ?    12 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Why different Pressure switch used in marine boiler water circulation system

1759


I need the recommended size for a 3 phase transformer at 13.8 KV Primary and connected loads of 3000 kVA at 4200 volts and 2375 kVA @ 480 volts AC.

2009


Why field rheostat is kept in minimum position?

1232


does the Trivector Meter of three phase automatically takes care of the low power factor and gives the reading accordigly or it does not take care of the Power factor while giving the readings please explain

1908


What is the emf equation of a transformer?

1248


what shoud be strength and weakness to impress interviewer????????

2058


how a flip flop can be used as a latch?

1981


Can anyone tell the proper diagram of star delta starter????

1923


we have one oven for 12 zone we are installed ir lamp in oven we control load from thyrister and 0 to 5vdc so our zone no 8 getting bright in fraction of second so what we do.. Please answer

1727


what is the difference between active power and reactive power and apparant power in practical as well as theoritical

1921


The slip during plugging operation is given by= A 1-s B 2+s C 1+s D 2-s

2835


how to introduce yourself

2026


WHY IL=IPH IN STAR AND WHY IPH=IL/1.732 IN DELTA? WHAT IS REASON BEHIND IT?

6343


How time response of the system is divided?

1185


what is high - pot test. what's its use?????

2179