Answer Posted / itsme
1. find load.... 8kw shower
2. find current Power/voltage ie. 8000/230 =34 amps
3. Use next fuse size up from current...40amp fuse/breaker
4. select a size cable suitable to carry 40amps
5. Find length of run. ie 20 meters.
6. carry out volt drop calculation
design current (34amps) x Length of run (20 meters) x
millivolt drop per meter (7.83 mvolts/meter for 4 square
cable) >>> 34 x 20 x 0.00783 = 5.44 volt drop!
if volt drop exceeds 9.2 volts use bigger cable
Is This Answer Correct ? | 23 Yes | 5 No |
Post New Answer View All Answers
all interview questions with answers of ntpc (2000-2009
different aspects of voltage stability
How to test lightning Arrester?
why the pf of semiconductor device is improved the electrical devices
use of PIR in ehv breaker
Why have to use copper cable for local isolator to motor ?
Can the output voltage of a rectifier be greater than the input AC voltage without the use of any voltage multiplier in the circuit??please provide the explanation too..
How do we calculate over and under frequency tolerance from generator data?
What kinds of decision are made about CT from it's Knee point(voltage & current)?
If a 3 phase induction motor is in off condition in the conveyor and rotor of the motor keeps moving with the conveyor than the resistance of windings of motor varies. why is it so ??
What are high pass filter and low pass filter? and What are the flowmeter ?
Explain the working of any one cutting machine
Define what is the function of anti-pumping in circuit breaker?
what is the path of thunderlightening? once both a buffalo and a person were standing 5m apart but lightening hit and killed buffalo not person?
if we give 60 hz single phase supply to the transformer used in europe , than what will happen