what's transient & sub- transient reactance means?
Answer Posted / steven karris
These terms appear in the calculation of fault currents.
Common sources of fault currents are rotating machines,
i.e., motors and generators. An important factor in
detrmining the magnitude of a fault current is a variable
reactance that changes rapidly after the initiation of the
fault until it reaches a steady state.
Subtransient Reactance, usually denoted as X''d (X double
prime sub d), is the reactance used to determine the
current during the first cycle after the occurance of the
fault. In about 0.1 second this reactance increases to the
level known as Transient Reactance usually denoted as X'd,
and after 0.5 to 2 seconds it increases to the leven known
as Synchronous Reactance and denoted as Xd, and this
determines the fault current after a steady condition is
reached.
| Is This Answer Correct ? | 205 Yes | 27 No |
Post New Answer View All Answers
CALCULATE THE TOTAL VOLTAGE DROP AND SELECT THE CABLE SIZE IN MM-SQARE FOR A PANEL-262KW AT 110 METER FROM THE SOURCE SUPPLY , SUPPLY VOLTAGE 240/415
what is difference between bus coupler and auto transfer switch
what is the role of transistor in Circuit?
How to justify this statement ??? "Capacitors in series provide less capacitance but higher voltage breakdown rating for the combination"
Draw the line diagram of diffretial relay connected to transformer?
Is it true that in the 3 phase transformer, the limbs of the core are at 45 dgrees to each other. if true, why?
please send privious years question papers of jindal steel and power ltd.My e mail id is rajanikant.sngh@gmail.com
how can tell us the AC indoor or outdoor which Tr and formulls
detailed procedure how we calculate cost for pcc m10 and rcc m20 including centering and labour excluding steel/ iron
What are the factor to be consider for CT selection in 132kV substation?
How one can check the MAIN of a house wiring ?
How impulse levels are calculated that for 11kV impulse is 75kvp, for 24kV impulse is 125kvp ?
What are the relays in ACB and VCB
how invertor convert the dc into ac give brif detail
Can we use Ccapacitive voltage transformer directly for metering purpose?