what's transient & sub- transient reactance means?
Answer Posted / steven karris
These terms appear in the calculation of fault currents.
Common sources of fault currents are rotating machines,
i.e., motors and generators. An important factor in
detrmining the magnitude of a fault current is a variable
reactance that changes rapidly after the initiation of the
fault until it reaches a steady state.
Subtransient Reactance, usually denoted as X''d (X double
prime sub d), is the reactance used to determine the
current during the first cycle after the occurance of the
fault. In about 0.1 second this reactance increases to the
level known as Transient Reactance usually denoted as X'd,
and after 0.5 to 2 seconds it increases to the leven known
as Synchronous Reactance and denoted as Xd, and this
determines the fault current after a steady condition is
reached.
| Is This Answer Correct ? | 205 Yes | 27 No |
Post New Answer View All Answers
As we know induction squirrel cage motor torque Directly praprortinal to applied voltage in star connection & delta also. If I connect 55KW Motor to DOL starter in load condition does motor withstand the load & what will be the current withdrawn ? motor will not fail ?
How to Calculate The Neutral Earth flat design calculation for the Synchronised generator (Gen 1-650Kva, Gen 2-725Kva
Why to keep capacitor bank off while generator running.
Installation method of self treated earth electrode.
how to calculate transformer turn primary & secondary side 11kv to 420v
WHAT IS ELECTRICAL MAINTAINTENCE ?
What is the count of hvdc transmission lines in india?
What are root loci?
How to calculate approximate load loss of a distribution transformer by knowing %ge imp of transformer?
Single line diagram for dbb (double bus bar)system.
How to calculate the Efficiency of Chiller
Why do we use copper cable for HT Supply and why not Aluminium?
In single phase capacitor motor, if the motor rotate reverse direction then how much power will be consumed by the motor and why?
What is the reason behind current flow(20 A) in amain earth cable of an SMDB? Is cuurent flow(45A etc) through a neutral cable acceptable?
what precautions to be taken while desigining a LT,HT panel. Eg-LT panel PCC panel with ACB installed. HT panel VCB panel with VCB installed. & what is main diffrence betwn IP54 & IP55 construction of panel.