I am an electrical power engineer and arranged power system
for a data center, I installed MCB, ELCB and erthing system
TN-C-S.
But some times several ELCBs Disconnect circuits at the
same time! what may be the reason? (the ELCBs are 25A ,30mA)
Answer Posted / chandra
Mr. Mehdi, Do check the neutral of all circuits wether they
are connected to same ELCB group. If one neutral from one
group is connected to other group this problem will occur.
Even though all neutral is common at final point, each
neutral will have to pass through the ELCB in order to
monitor the return cuurent.
Is This Answer Correct ? | 10 Yes | 0 No |
Post New Answer View All Answers
WHY THE COLOR OF OUTDOOR TRANSFORMER IS BLUE ONLY???
What are the symptoms of a bad PG card of a drive (inverter) esp. of Yaskawa Ac Drives (inverters) G7 ?
sugest any typical project ?
what is the benefit of floating our DC source? if i have two floating DC source of which 1 has a ref voltage of -21VDC and the other of -18VDC. can it be connected in parallel to share a common ref voltage? if not, how do i make both sources to be of common ref voltage? tks
please send me jindal previous aptitude and technical question and answer.my email id is deep_raj@live.com
How many devices can be connected in one zone of FACP
What is the function of the circuit breaker failure relay?
a 100mva,400/200v transformer has leakage impdce of 10% draws a steady state line currentof---------------
hey guys help me out.....what are the industrial uses/functions of nozzles in industries
Whats the minimum value for I.R. that can be allowed for HT & LT alternators for operation?
Dyn1 transformer vector group testing how to do
what is meant by impedance & transient protection?
how we can do the insulation on secondary of ct explain and so that tan delta will within limit
I had applied for JE in PSEB, Can you pls send me the Question bank for related to my field
PAC and simple Ac different