6 MVA transformer secondary is rated for 725V at no load.
The incommer ACB is rated at 690 V, 3200 Amp. Would there
be any effect on performance of ACB due to lower voltage
rating?
Answer Posted / mnm
Your selection is OK. Any breaker will have 110% voltage
withstand capability. Only thing is interruption capability
reduces, which is not relevent on no-load. On load, the
voltage of the transformer will reduce by nearly 6%, due to
impedance, making it just suitable.
Is This Answer Correct ? | 1 Yes | 1 No |
Post New Answer View All Answers
How can ou verify the size of conductor 50Sq.mm ACSR
errection check list for transformer maintenance
Factory acceptance test. FAT. For 132 kv transmisstion towers what is that meaning and what are the tests commonly companies perform now days.
If we have use two power cable for incomer, that time how many use cbct for earth leakage protection? 1 or 2 if 1 way? If 2 way?
Is it possible to measure the voltage of a battery from a single terminal?
In how we connect watt meter for open & short circuit test of a single phase transformer.
How it can worked plc based electrical system And which type of software using.
How to test the Secure Elite 440 Multi function meter working condition.
why co incidence factor considered in transformer sizing?
how we start 40w tube light with 4 diodes,2capacitors,1 choke and without starter.(a product avilable in market which lights burnt tube lights also)
How to choose size of the cable w.r.to current carrying capacity ...
sir,in our plant we r using SATEC PM172E power reading meeters in HT panel side it is monitoring the MB data smart viewer(sever).but last one week we did not get readings inthe server only available in meeter.tell me how communicate meter and server. and also what steps we take for checking.
what is the concept of directional power?
we have 15 ampere variyac but we want 30 ampere variyac what we do
power transmission pole used one support , that only for support or earthing