6 MVA transformer secondary is rated for 725V at no load.
The incommer ACB is rated at 690 V, 3200 Amp. Would there
be any effect on performance of ACB due to lower voltage
rating?

Answer Posted / mnm

Your selection is OK. Any breaker will have 110% voltage
withstand capability. Only thing is interruption capability
reduces, which is not relevent on no-load. On load, the
voltage of the transformer will reduce by nearly 6%, due to
impedance, making it just suitable.

Is This Answer Correct ?    1 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How can ou verify the size of conductor 50Sq.mm ACSR

1644


errection check list for transformer maintenance

2299


Factory acceptance test. FAT. For 132 kv transmisstion towers what is that meaning and what are the tests commonly companies perform now days.

1437


If we have use two power cable for incomer, that time how many use cbct for earth leakage protection? 1 or 2 if 1 way? If 2 way?

1806


Is it possible to measure the voltage of a battery from a single terminal?

1372






In how we connect watt meter for open & short circuit test of a single phase transformer.

5988


How it can worked plc based electrical system And which type of software using.

1805


How to test the Secure Elite 440 Multi function meter working condition.

1739


why co incidence factor considered in transformer sizing?

1551


how we start 40w tube light with 4 diodes,2capacitors,1 choke and without starter.(a product avilable in market which lights burnt tube lights also)

1768


How to choose size of the cable w.r.to current carrying capacity ...

1828


sir,in our plant we r using SATEC PM172E power reading meeters in HT panel side it is monitoring the MB data smart viewer(sever).but last one week we did not get readings inthe server only available in meeter.tell me how communicate meter and server. and also what steps we take for checking.

1921


what is the concept of directional power?

1670


we have 15 ampere variyac but we want 30 ampere variyac what we do

1561


power transmission pole used one support , that only for support or earthing

1553