6 MVA transformer secondary is rated for 725V at no load.
The incommer ACB is rated at 690 V, 3200 Amp. Would there
be any effect on performance of ACB due to lower voltage
rating?

Answer Posted / mnm

Your selection is OK. Any breaker will have 110% voltage
withstand capability. Only thing is interruption capability
reduces, which is not relevent on no-load. On load, the
voltage of the transformer will reduce by nearly 6%, due to
impedance, making it just suitable.

Is This Answer Correct ?    1 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Name a govt approved university which have 100% online engineering course.

1279


How will you utilise electrical power? You can start from the generating station.

1461


What are dependent sources?

672


at meter room 50 hrc switch installed,but there are not get earthing proper,so what happen?and 11kv transformer out put going in to hrc main 400a three nog each? so earthing is require for all switch? (some customer made earthing at there home.)

1475


give me atleast four differences between circuit and network

1732






What is Anemometer used to measure?

687


What are the raitings of Mcb,mccb and Acb in detail ??

1110


What is shutdown of electrical sub station?

1961


how does a liquid starter reduce the starting currents?

1682


In a 3 phase 4-wire system. For a 3.5 core cable if all loads are single phase and balanced, what will be neutral current? will it be sum of all phase currents? Or it will be zero? And if loads are unbalanced what will be neutral current?

1260


What are the specifications for getting approval of Substation?

1441


What is the difference between solid grounding and impedance grounding?

1548


Differentiate between induced emf and self inductance?

614


how to calculate units consumption for a 12 hp motor /hr.

1043


difrent between vcb acb sf6 and mccb breakers

4629