6 MVA transformer secondary is rated for 725V at no load.
The incommer ACB is rated at 690 V, 3200 Amp. Would there
be any effect on performance of ACB due to lower voltage
rating?
Answer Posted / mnm
Your selection is OK. Any breaker will have 110% voltage
withstand capability. Only thing is interruption capability
reduces, which is not relevent on no-load. On load, the
voltage of the transformer will reduce by nearly 6%, due to
impedance, making it just suitable.
| Is This Answer Correct ? | 1 Yes | 1 No |
Post New Answer View All Answers
Enlists the applications of sampled data systems?
how to select automotive wire by mathematical equation with given current, vlotage and resistance
How the capacitance og capacitor volatage transformer is decided?
A d.c. Shunt motor is found suitable to drive fans because they require?
1- What is the Polarization Index number be good for 15KV 3c#500MCM electrical cable? 2- Can I use the IEEE Std 43-2000 to perfom the PI test? Thanks
in 1-phase 230v,how in 3-phase 440v. in each phase in between 230v.
1.what is difference in maintain Hz again Hz in USA ? 2.how to calculate the battery AH? 3.why are yearly maintained in transformer how many tests in required?
how calculate gd2 of ht motors
Write down the name of 2 lady Bir Pratin of Bangladesh
I want d.g.set our company
how to check ac servo motor
what is the illumination level required for child play area?
Control wiring of a dol starter for forward and backward
Its possible to use 3core 2R of 240 sq.mm cable for 3phases & separely 50sq.mm 3core cable fully for Neutral for connection of PCC to MCC 3ph..4wire system?
why should the lowest unit of a testing transformer ( cascaded transformer ) have higher power rating??