Answer Posted / sunil bhat abb
Floating Neutral is a condition when neutral is not
grounded the case may be when single phase Cable say 66 KV
having lead sheath is not grounded at either side as a
consequence the Neutal end point (sheath ) develops some
potentail say 50 Volts under normal condition and in case
of fault due to transformer effct between sheath and
conductor the voltage of unearthed(floating end) end gets
abnormally high so a Lighting arrestor /surge arrestor is
used at floating end
| Is This Answer Correct ? | 11 Yes | 6 No |
Post New Answer View All Answers
What are the main advantages of generalized error co-efficients?
why we need to us lenz's law for synchornous motor
What range of speed can you get with the field control method of speed control of d.c. Shunt motor?
how to compare with Relay settings for HT< panels, RMU panel, and PSS CSS transformer?? 1) Load amps, 2)Tripping time, 3) CT ratio, 4)Cable size 5) Transformer KVA rating 6) transformer full load amps
0.5,1,1.5,2.5,4.0.6.0,10,16 square mm electrical wires how much take maximum current in 50htz
what is vtg limit of earth and neutral at transformer side?
we are having 15kw and 3kw motor both can run in same time , instead of using copper we are using ug aluminium cable , 35 sq.mm is suitable for its current carrying capacity..?
what is interfacing in computer studies?
How relay works, reverse relay, master relay, os relay, earth fault relay and what is its setting point
What is Bolted fault?
how generator load test is conducted?what are the steps?
How can we increase the capacity of Energy.?
What is the need of earthing transformer for delta side of a transformer. (Think of a line section between a star/delta transformer at a grid substation and delta/star transformer at a village. An earthing transformer is there at the delta side of the star/delta transformer at grid substation). As there are no ground reference there will not be fault current if a one phase is grounded. Further L-L phase will be sensed by the primary side of star/delta transformer as a L-G fault. So why an earthing transformer is required at delta side
what is size of 3phase 4wire cable to be used for 11 ton ductable A.C and how to calculate cable size for different load
Dear sir, my knowledge about cable size determination is limited. Though I read examples I could not calculate the Cable size required for electric driven pump 40 KW, 380 Volt, 50 HZ, 50 meter from transformer and it is three phase star delta starting. Please help as there is no one in my surroundings to help.