how manys ways dp transmitter can be calibrated having
range of -150 to 400mmwc,what side pressure u will apply?
Answer Posted / basil
TWO WAYS.WE WANT TO GIVE 150 MMWC ON THE LOWER SIDE AND
ZERO PRESSURE ON HIGHER SIDE AND SHOULD GET THE OUT PUT OF
4 mA.AND ZERO PRESSURE ON THE SIDE OF LOWER AND 400 mmWC ON
THE HIGHER SIDE AND SHOULD GET THE OUT PUT OF 20mA.
IF NO PRESSURE ON BOTH SIDES THE OUTPUT SHOULD BE 8.36 mA
(IF IT IS A 4-20mA TRANSMITTER)
| Is This Answer Correct ? | 21 Yes | 2 No |
Post New Answer View All Answers
Identification of control valve parts.
What is Positive Calibration and Negative Calibration?
what is the input to be given in digital flow meter during the the calibration time?
How works weighfeeders in cement industry? what is the working principle?
List three types Level Gauges with their working principles
Pressure tx shows 1 mbar but we need 1000 mbar at this process condition .. how can we sort it out .
-/5A. What is the meaning and limitations of this in energy meter constant. It is a 3 phase LT Energy Meter. If this Energy Meter is connected through a CT of ratio 200/5 Amps, then what is the multiplying constant and how its will be calculated.
hi! i want to know about mpse exam.
What you mean by multi stage control vavles?
Why we are using reverse action in displacer types level transmitters on some Vessels?
how to commission furnace ( water heater)
on interface level transmitter model(RTG3302-EMERSON) What is threshold valve how can we select correct threshold value T1,T2,T3,T4 When interface water & hydro carbon
how will you check torque value during Factory acceptance Test for control valve/ESD ON/OFF VALE how will you confirm this torque value is being correct, Which document will you be refer.
Which topics are covered in Process Control?
How process line mpm calculation is done?