In CDG type IDMTL realy O/L , E/F, O/C which are used for
out going feedrs,on R-phase o/c element, Y-phase , e/f
elecment and on b -phase o/c element will be connected .
Why the earth fault on center phase only, why not on other
two phases?
Answer Posted / gova
This is called 2 O/C+1E/F relay scheme.This scheme is used
mainly where the transformer connection is Dyn11.
please refer the current distribution in this transformer
when a fault occurs in feeder.
This scheme will be sufficient to clear the faulty
section.But nowdays 3O/C+1 E/F relay scheme also used in
many places
gova
| Is This Answer Correct ? | 6 Yes | 2 No |
Post New Answer View All Answers
in parallel operation of power transformer why the distance between power transformer and capacitor bank feeder is necessary to know
what is magnetizing and demagnetizing current in generator and motor?
Dear all i am kumaravel. now in chennai. my work is control and relay panel auto cad designing.up to 11kv to 400kv then question is i am improving my knowledge. i want some books name and auther are available for this C&R panel related. plese any one help me
What is meaning of out of phase (making & breaking) capacity And how to calculate
What is the different between conventional MCC and intelligent MCC? Common controller or controller for each bucket
what is the difference between pvc & fiber glass cables
Can anyone please give me the parameters , formula needed to calculate the circuit breakers for building services.Thanks
What do you mean by the zone of protection?
HOW MUCH CURRENT DOES SYNCHRONOUS MOTOR TAKES AT SYNCHRONOUS SPEED IN NO LOAD CONDITION ?
prove that power consumed in 3 phase delta system is 3 times as compared to 3 phase star system
What happens to voltage when current through the inductor is constant?
Explain the working of any one cutting machine
what is earth fault relay 64T, why it is used in main Incomer and neutral CT of Transformer.
why we are not giving the zone 1 trip command to the master trip relay
how is calculated the quantity of weight in hot test xlpe?