i have 28/32 MVA power transformer with 11/6.6 KC voltage
rating and 12%impedance.it have star connection at both
side.but it have another thied winding tertiary
winding.what is used of this winding.
pl tell me
Answer Posted / ajay patel
How your tertiary Winding is connected? what is the rating?
If all three phase terminals are bruoght out then it can be
used as additional seondary winding. But If this tertiary
is connected in Open Delta & 2 termianls of open delta
brought our for Earthing. That means this is installed for
Harmonic purpose. If you have rectifier, Big VFDs or such
load which can generate Theird Harmonic in big amount then
these third harmonic can be reflected in entire Grid, if
your transformer is Star - Star. Which is may damage other
equipments / consumers also who are connected with same
supply. Hence it is necessory to control 3rd harmonics in
grid. For this you can provide Delta Primary for
Transformer. But you dont have delta in primay tehn you
have to provide Tertiary winding with open Delta. This Open
delta is closed out side of Transformer & Complete Delta is
formed. This Delta winding should be earthed to minimise
harmonic disturbance in the system. Please check, do you
have earthed tertiary? Is it in Delta?
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
What is the difference between relays and contactor construction wise?
in general it is observed in power stations, the tertiary winding is used in higher rating Y-Y auto transformer but not in Y-Y power transformer. is the tertiary winding is compulsory then why it is not using in power transformer
Please brief me about number of pole in alternator.In single phase alternator coils are connected in star or series. How to calculate frequency for the same.
66kv under ground cable how to layaing in ground any special case two ckt r runing
How to setting the volume of RTCC panel AVR (11kv) controller
Give the topology of current amplifier with current shunt feedback?
one conductor length is L.and i am strech uniformly this conductor and made length is 2L.so resistance of this strech conductor is R=4R..but i want to know about area of stech conductor hows it become a/2..
the problem faced on star or delta winding connection??
hello friend i wish to study a course related to the electrical construction, controlling and monitoring , which course i want to study? pls give me the name of institute?
What is process of anneling transformer core
What is the difference between multimeter
how can we change the polarity of Alternating current rapidly? how frequency of ac can be controlled and changed easily?
How to calculate that clean water supply in one Day from 150 KLD STP?
Mention the disadvantages of low power factor? How can it be improved?
Why line VTG = √3 phase VTG in star? How?