What is the difference between AMF panel and DG
Synchronization panel? please define the working of both
the panels?
Answer Posted / ravikumar josyula
AMF Panel: is Auto Mains failure panel. When the EB power
goes off with a time delay signal will go to DG self
starter to start the DG. And when the EB power
resumes,after definite time delay stop signal goes to DG
and EB supply contactor will become ON.For a fraction of
time power will not be there for the utilities.
In synchronization, there is no outage of supply to the
utilities.When the incoming genset is to synchrinize with
the existing set,we've to match the magnitude of the
voltage, phase angle and the frequency and then only we've
to switch on the incoming set's breaker.
| Is This Answer Correct ? | 85 Yes | 10 No |
Post New Answer View All Answers
plz send me the procedure and syllabus for mseb exam
How can maintain our H.T. motors used in cement plant. please send me procedure.
we have amp, voltage, kw, length detail then how to calculte copper & alluminium size of conductor of 3-phase induction motor
What is the earth treantment procedure?
What are the Return ( Monthly / quarterly/ Annual submitted to Electical Inspector for an establishment (Factory in Maharashtra-- Small scale category having seperate HT line of 22KV ) as per Maharashtra Electricity Act
What is NGR . What is the purpose of 10 sec ,60 sec rating of NGR.
my diploma certificate in my higher education college
What are n circles?
What's mean HVF & HAF in Vacuum Circuit Breaker?
Do u know any one? how to find out in motor rated amps? formula?
A TRANSFORMER 440/400V,DELTA/STAR CONNECTED.THE NEUTRAL CONNECTED WITH GROUND CABLE THAT IS DIRECTLY CONNECTED TO THE PANEL,FROM PANEL IT IS CONNECTED EARTH PIT.IS IT RIGHT? IF IT IS RIGHT LEAKAGE CURRENT AFFECTED.SECONDATY IS PROTECTED WITH EARTH LEAKAGE RELAY.
what is the difference between transformer,converter and transducer
How the setting of the vector surge relay shall be calculated when the relay is to be used for Grid islanding application?
What is difference between insulating medium and fault current interruption medium in a switching device.
i have faced a problem in ro plant grunfos make bm30type pump it is 22kw pump. We start this pump using siemens 3rw 4423-ibc44, 30kw softstarter but this soft starter will frequently failier so we planed to change dol starter. So pls tell anybudy its possible or not.