We have ZR22G-100-S-A-E-T-T--E-A/CV/F1 Model Zirconia
Oxygen analyser which is Yokogawa make. I kept the analyser
in Flue gas path at Air pre heater area. My plant is 7.5MW
Biomass power plant. For a particular fuel, Coconut Husk
which contains Sodium and Potassium chlorides iam not
getting proper reading, Analyser output always Zero. I
calibrated the analyser and it is OK. For Other fuels like
Wood chips, Cholam waste, DOB, Groundnutshells, Ply wood
waste and all iam getting actual percentage of Oxygen. What
is the main reason behind this draw back?
Answer Posted / tarique
please check your heater which is used in zirconia
change your load air percentage in firing and observe
changing or not if changing means actual is zero
| Is This Answer Correct ? | 6 Yes | 0 No |
Post New Answer View All Answers
what is performance test.need defination
State bernoulli’s application.
What is offset in a control system.
Valve positioner and actuators in detail.
What are different types of valves?
field bus transmitter calibration procedure tell me
For what reason would you possibly be compelled to make use of a Smith Predictor. Explain the idea behind the operation of this device.
how 3 out of 2 Logic/interlocks works? give brief explanation with help of diagram.
what is exact time to study dcs and plc cources
IS there any effect of vortex in low pressure side of the transmiter after the orific in feed water line? if yes then what is the calculation?
How vortex sensor used for steam flow measurment can be checked on line i.e without taking out from process line.
Which tank weighing system is better to install (Accuracy point of view) 1) Tank weighing system with 3 load cell or 2) Tank weighing system with 4 Load cell
all types instrumentation questions want
Isometric drawings are generated during _________________ phase of a project
Difference between ultra sonic flow meter