How can we calculate the rating of capacitor bank to be
connected for a particular load(ex.100kw)to improve the
power factor from 0.8 to 0.9?
Answer Posted / ravikumar
kvar=kw(1.732) (TAN PHI1-TAN PHI2)
HERE PHI1=0.8
PHI2=0.9
THIS IS THE FORMULA REF; powersystems v.k. mehata
| Is This Answer Correct ? | 7 Yes | 5 No |
Post New Answer View All Answers
In control room of our one plant there is a continuously the incoming power goes to PC is vary,means in stabilizer it continuously indicate from high input to low and low input to high. what is the reason and its solution.
what happens if earth of 33kv cable is not connected to earthing pits? please send this query's answer to ngrm.sudha249@gmail.com
i am going to give the JSEB,RANCHI exam for power plant,so i need some samples of papers related to that,so please send me these papers by my mail id.
What is maximum power transfer theorem?
1)how to reduce the value of tan delta of trasformer and CB,bushing,CT&PT,CVT ? 2)how to reduce the resistance of CB contact and its operating time? 3)plz.....send me the project report on conditioning and monitoring of substation equipment on my email id (gusaiyogendra03@gmail.com)
what is the effect of change in supply frequency on load angle of synchronous motor,all other parameters remaining same?
how to maintain frenquncy with syncronising sub-station for distribution
why constant voltage transformer should be start without load? and if started then what will happen?
What does bode plots shows?
can anyone explain 11kV 3core cable megger,hi pot test procedure with connection details?
we are going to install a solar PV site and how can we calculate PV Solar Panel Efficiency, can anybody tell me complete method for its calculation.
what is the use of sdf?
How DC earth leakage currents can be reduced ?
High voltage test procedure of in swgr board. why should measure millivolt drop on testing time?
11 kv input, 66 kv input advantages