Answer Posted / khalid hussain shaikh
POWER=1.732*VOLTAGE*CURRENT*POWER FACTOR
HERE POWER=2500KVA
VOLTAGE=11 KV
POWER FACOR AS STANDARD=0.85
I=?
I=2500KVA/1.732*11KV*0.85
KV CANCELLED EACH DENOMINATOR AND NUMARATOR,
I=2500/1.732*11*0.85
I=154 AMP (11 KV SIDE)
I=2500 KVA/1.732*415 V*0.85
V CANCELLED EACH DENOMINATOR AND NUMARATOR
I=2500 K/610.963
I=4.091 KA
I=4091 AMP
| Is This Answer Correct ? | 10 Yes | 16 No |
Post New Answer View All Answers
How servo stabilizer works.
there are cam operated switches - why we call cam operated , What is cam ?
During underground cabling in landscape area what did we cover the cable with to prevent the electric shock & protect the cable?
wow to calculate the transformer rating(KVA)
How energy is generated in hydroelectric power plant?
What will happen if the d.c. Shunt motor opened accidentally running on no-load has its shunt field winding?
what will be the effect if you were using different brands of outlets?
Do inductive loads have distorted current waveforms ?
What is notching in dc machine?
WHat is the requirement of installing FAST ACTING EARTH SWITCH in GIS and how is that integrated with protection system. How and when does it operate?
i have seen one 8.4 MW synchronous motor in a plant located in bellary it is fixed with brushless rotary rectifier ,anybody can explain its start up principle
What is George phenomena to start the synchronus machine?
An 8 pole, 50 Hz, 3-phase IM is loaded to a poing where pull out torque will occur. The rotor resistance per phase is 0.3 ohm and motor stalls at 650 rpm. The slip when motor stalls is A 1 B 0 C 13.33% D 10.33%
Differentiate between magnetic field and magnetic flux?
what is the internal working of star delta starter