Answer Posted / sathish n p
Take an example let tr rating is 2500KVA, 11KV/415v
TO calculate maximum loading on primary side
2500 X 10^3=1.732 X 11 X 10^3 X I
I=131.01Amps
Similarly Secondary side
2500 X 10^3=1.732 X 415 X I
I=3478 Amps
Is This Answer Correct ? | 33 Yes | 5 No |
Post New Answer View All Answers
What is the minimum underground tank size capacity considered for firefighting purpose?
ult of expression 'document.FrmQF.myem
when we have to use UPF wattmeter and LPF wattmeter? what is the difference between UPF and LPF wattmeter in terms of construction?
some time we open engine breaker 8.0 MW load but plant not trip. and another time engine open 4.0 MW load engine trip why? individually engine breaker open & individually emergency stop why difference?
why sielent pole is used only in hydro generators and not in turbo generators
List of equipments required foe industrial repair lab.
What is the role of power pack in substation protection system?
why capacitance effect is predominant in underground cable transmission and inductance effect is predominant in over head line transmission?
what shall be no load voltage of 132/33 kV transformer ? is it 33 kv of 34.5 kV
what is the difference between switchgear and circuit breakers and is there any difference between outdoor and indoor switchgear and circuit breakers , and how would you differentiate between switch yard and substation and grid station . thanks
how to size H.T & L.T Panel ?
wht is embedded systems? what is new inthis field?
what causes contact chatter when there is no demand on the air conditioning unit?
All tape of electrical questions Answers tape of motor transformer e.o.t crane
WHERE NEUTRAL WIRE IS CONNECTED AT DOMESTIC TO TRANSMISSION LINE(SINGLE PHASE TO THREE PHASE)