Answer Posted / sathish n p
Take an example let tr rating is 2500KVA, 11KV/415v
TO calculate maximum loading on primary side
2500 X 10^3=1.732 X 11 X 10^3 X I
I=131.01Amps
Similarly Secondary side
2500 X 10^3=1.732 X 415 X I
I=3478 Amps
| Is This Answer Correct ? | 33 Yes | 5 No |
Post New Answer View All Answers
What is inrush current? how can calculateit? what is the affect of it?
We have two APFC panels in same station. I need how to connect CT in two APFC panels.can we take one CT in series connection or two separate CTs.
WHAT IS THE WINDING PROCEDURE OF ELECTRICAL MOTOR
What is the difference IN MCCB's between thermal magnetic and electronic tripping system ?
In case of HV test on medium voltage cables, BS is asking for 4 U0 where as IEC is asking for 3.5 U0. Can any one advise me how this 3.5 times or 4 times U0 is derived?
What should be the percentage increase in length of the dead end clamp for bus bar conductor (Hawthorn) after hydraulic pressing and what should be the applied pressure?
how much leakage current is allowed in MC61A L&T make relay?
Anybody tell me about modbus hex address of l&t trivector meter er300p??I want to read voltage,current,kwh etc via rs485...If anybody have a manual then send on my mail..Brijeshmodi18@gmail.Com
What is the form name of 'c' license, I want to download in web
What is dc current source? Differentiate between ideal and non ideal current sources?
why ht cable end termination don't have a gland?
i had aplied Hindustan Petroleum corporation limited for the post of maintenance technician -Electrical,i want model questions,if anybody have please send it or please advice?
HELLO SIR, IAM PREPARING HPCL EXAMS. SO PLS SEND MATERIAL OF HPCL ELECTRICAL ENG..TO VIJAY_8888@YMAIL.COM
What is the name of transformers oil filteration equipment?
what is smart grid? why we use it? explain in detals bcoz i want give presentatin from it....