On load tap changer (OLTC) explode?
Transformer
Vector group: Ynd11
Rated Power: 353MVA
Rated Current: 693A
Voltage:294/20KV

OLTC
Type: T III Y1000 110/c 12193w
Max Operation Current: 295A
Step Voltage: 550V
Arrangement in Tx windings: Y Connection

Problem: Damage of Unit 1 Generator Transformer On Load Tap
Changer (OLTC)

Description of Incident:
9.00 a.m. :- Generator No Load test on excitation system
started

10.30 a.m :- Carried out AVR change over
test

11.30 a.m :- Preparation for Generator Manual Synchronizing
test


12.00 a.m :- Manual Synshronizing test started.
Observed incoming generator voltage higher than running voltage.
CECR operator operated Generator Transformer OLTC to bring down
the incoming generator voltage

12.03 a.m :-Generator Transformer abnormal alarm operated at
Gen.Control Desk (CECR)
CECR operater at Generator transformer bay informed that the
transformer
oil splashed out from OLTC.
CECR operater informed that he heard explosion inside OLTC.
Observed Oil level & Oil Flow alaram operated at Tranformer
local annunciator.

12.05 am :- CECR operator 'Open Gen Field Breaker”

12.10 a.m. :- Elec1 team inspected the OLTC and found the
OLTC rupture disk was broken
and oil spilled at OLTC area.
- Elec1 found the OLTC top cover bulging.

Do anyone know why and possibility cause happen in this OLTC.

Answer Posted / j.ikesavan

my friend please check your inter lock system how to
working motor on load tap changer your winding failure its
going up and down voltage thats why this disc is breake.

Is This Answer Correct ?    1 Yes 4 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

please send me the previous year's question papers of jindal GET exams

5524


I have 1500/1A CT If i connect this CT in 6.6KV bus bar means what will be the voltage present in CT?

1586


-What shall be short circuit current of LV switchgear for a 1000 kva, 11.415kv, 3 phase tranformer with 5% reactance.

1682


What is the minimum IR value of HT/ LT cable? Pls post separetely!!!!!

1950


What is “pu” in ee?

650






Cb closed condition if there is a tcs fail whether cb will trip or not

1323


write circuit diagram for a motor rotate in forward direction once it started and when pressed the same button it should rotate in anticlockwise.

2072


what is meant by LCR meter? where its useful ?

1585


in parallel operation of power transformer why the distance between power transformer and capacitor bank feeder is necessary to know

1373


What are IR values and what it should be for coil and for insulator

2522


Do you know what is dry-out test in x'mer

2218


For a three phase induction motor, what will be the effect on motor if the neutral of the system is shifted to say 20 deg.?

1406


ELECTRICAL ENGINEER TEST IN FEWA ANY ONE HAVE KNOWLEDGE ABOUT THIS?????????

566


What are the basic elements used for modeling mechanical rotational system?

625


what purose of the double circuit transmission line phase of the line phase changed for circuit-1 for Circuit-2 R-Y-B B-Y-R

1822