how to calculate the battery Ah? what is the formula.
Answer Posted / ramakrishnan
AH = (VA * Power factor)/(Output Efficiency * Vdc * K)
K is diversity factor
for 30 mins back up 0.9
60 0.5
120 0.3
240 0.2
Efficiency is 0.9
Pqwer factor is 0.9
Any doubt about UPS contact
98409 92005
| Is This Answer Correct ? | 28 Yes | 39 No |
Post New Answer View All Answers
What is called limb of a transformer?
What are the relays in ACB and VCB
what is meant by IGBT how they differ from tyristor ?
What are the advantages & disadvantages of a group electrive drive?
what is effect of leading power facter on the system and billing
how much flux density of CRNO core
Pl. brief about break-down maintenance of machine tool.
What are your future plans for the company if permanently employed?
A system absorbs 100 k J of heat and the increase in its internal energy is 100 kJ; the work done is
what happen when power factor of 2 parallely operated transformer become equle?
In single phase ac ups supply when current is measured with tong tester neutral current is found more than phase current.What is the reason?
1. A 380 / 220 V r.m.s. 3-phase 4-wire circuit carries loads of 8 + j8.1 ohm; 4 + j4.1 ohm; and 2 +j2.1 ohmin the three phases respectively. The length of the circuit is 100 m, and the resistivity of the phase conductors is 0.0005 Ω/m. The neutral conductor is of the same size as the phase conductors. a) Select a reference angle 0for the first phase. Then write down the three phase voltages in both polar format and complex number format. b) Make appropriate assumptions, and take temperature effects on resistance is insignificant. Calculate the currents in the three phases. (Note: Determine conductor resistance, and apply Kirchhoff’s Voltage Law) Based on the result, suggest a main switch rating for the circuit. c) Show your preferred direction of neutral current in a diagram, and then determine its value. (Note: Apply superposition principle, and Kirchhoff’s Current Law) Use its magnitude to show that in this circuit, the unbalanced load may increase the voltage drop in some of the phases. (Note: Also observe the common volt drip in neutral) State your assumptions, if there are any. d) Suddenly the neutral wire of the circuit is broken. Estimate the new currents in the first phase, i.e. Phase L1. State your assumptions, if there are any.
how to select electrical equipment such as fuse,dg,transformer,motor,msb,wire,cable as per the connecting load..please mention any books to design,take licence
what is the meaning of the symbol << >> put in transformer drawing
We have 90mX100m hangar with 16 no.of supporting pillar. It is required to provide power supply on all pillars. what is suggested earthing scheme for hangars.