Hai I have 2500KVA,Transformer,13.8KV/380.DELTA/STAR.How
much load that I can take interms of current?How can I
calculate also when I have loads in KW?
Answer Posted / shalini.b
Transformer Ratio is given by
k=(v1/v2)=(N1/N2)=(i2/i1)
where
V1 : voltage at the primary side
V2 : Voltage at secondary side
like wise for current(i)& Number of turns(N)
k= V1 /V2
= 13800/380
=36.31
P=1.73*V*i*cos(phi)
input power
p1=1.73*v1*i1*cos(phi)
i1=(2500*0.8)/ (1.73*13.8*0.8)
= 104 Amps
k = i2 /i1
So i2 = 104*36.31
=3776
| Is This Answer Correct ? | 15 Yes | 6 No |
Post New Answer View All Answers
what purpose to use excaiter in DG.?
bsec exam syllabus (mis)
What is the tube exial fan?
Please nybody say, weather the result of Bharat Oman is declared or not? Probable date of declare???????
What are n circles?
hi guys please tell me the procedure for mesuring the coil resistance of 3ph induction motor?
The synchronous machine excitation system explain
What is the relation between frequency and motor rpm?
What is meant by RVT and NDR ? expansion and details of it
does buccholz in a transformer use batteries
I am having a 1500 KVA transformer whose secondary current is 2086A and my connected load is 1000 KVA, I am having 400 KVAR APFCR for PF improvement what ratio of CT should i install in LT EB Bus to get optimum PF improvement?
What is mathematical model of a control system?
some time we open engine breaker 8.0 MW load but plant not trip. and another time engine open 4.0 MW load engine trip why? individually engine breaker open & individually emergency stop why difference?
HOW WE CHOOSE EARTH'S POTENTIAL AS ZERO V?
What is the rating of a circuit breaker needed for 300 kv load in 33KV supply line of 33/415 transformer ? Whether 800/1200 amp vaccum circuit breaker can perform for a 33 KV line in input in 415 volt in output of the transformer ?