Generally in AC we consider voltage, frequency and phase
sequence for parallel operation ... Can we parallel two DC
battery chargers? If yes, then what precaution to be taken
when we parallel two DC power?
Answer Posted / vijaykumar shetye
1) Yes, theoretically, we can parallel two DC battery
chargers, but generally they are not designed for parallel
operation.
2) Following factors are to be considered.
1) The voltage of both the chargers should be the same.
2) Both chargers should be connected in the same
polarity.
3) The output impedance of both the chargers should be
the same, so that both deliver equal current. (It is not
necessary that both the chargers should be of the same
make. It would rather prefer same model than same make.)
4) The characteristics of both the chargers should be the
same. Both should be set at the same current setting for
changeover from boost to float.
5) The current capacity of both the chargers should be
the same.
| Is This Answer Correct ? | 12 Yes | 0 No |
Post New Answer View All Answers
Hello sir i m student of gtu .what is idp.
What is Plank's Law?
what is meaning of 230volts ac 50hzs ac supply is it rms or maximum to getting ac 230v what amount of max voltage they will send
how current is reverse from its normal direction during the fault?
explain which quantities change in the starting and the and the running condition in induction motor
what are the parameters plays a major role in Potential transformer Burden calculation??
what is the formula for computing cable tray size & capacity
I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?
How can calculate the rating of a alternator for a given specific load with formula
I want to know the 'Test voltage' for Tandelta testing of 3.3 / 6.6 / 11 KV Motors. Please explain
What happen when neutral point connected to core balance current transformer? (Neutral point of an alternator of a 180KVA DG. Neutral point connected to CBCT means enter to the CBCT)
how could we know the size of cable by physical view?
what should be the ideal gauge of wire (In sq mm) for different loads in Ampere?
what is the difference between c power and U power acb breaker
what are the principles of a booster converter?