Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how to calculate capacitor bank value to maintain unity
power factor plz xplain with some suitable xample?

Answer Posted / shalini.b

capacitor bank value is calculated in KVAR
From Power Triangle,
KVAR = Sin(phi) * KVA

Desired Power factor = 0.96 (say)
cos(phi)=0.96
phi = cos(inv)0.96
phi= 36.86
Sin(phi)= 0.28

If the transformer rating is 1250 KVA (say)
KVAR = 0.28*1250
= 350

Is This Answer Correct ?    22 Yes 8 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

why any centrifugal blower draw more current in starting. consider id fan and fd fan?

1854


How is the gain affected by the introduction of feedback in a control system.

1159


How to Prepare preventive maintenance shedule of machine tool.

2016


mccb service sittings be done?

1947


HOW TO WORK A VFD?SAY SIMPLE METHOD

4413


WE HAVE THE DC RECTIFIER 1500A, INPUT VOLTAGE IS 3 PHASE. HOW TO CALICULATE THE LOAD? 3 PHASE SIDE EITHER dC SIDE. PLEASE SUGGEST ME

1873


what is the use of surge suppresser in 33 KV incoming panel. where it must be installed,inseries with incoming cable surge suppresser must be at incoming of the breaker are outgoing of the breaker

5405


what is the operating time for LBB and how does the LBB relay realise whether cb is opened or not?

1975


difference bewteen reverse current and alternating current

2220


234 MVA Generator 3 phase Short circuit current Values required? Gen set Rating-234 MVA, Gen Voltage-18kv, PF;0.8, Xdv:23.5 %, Transformer Rating-18/380KV, 680MVA,Yndd1 two winding, Step up TR, ZT:35.50 %,X/R 4.33 Gen CB Position, CB open ,Disconnected open, Generator Running Voltage 18 Kv, Bi mistakes generator side earth switch Closed during that time short circuit current level in 3 Phase required, and how to test on site 234MVA Generator Short circuit current,

2222


how meger function

2881


What is the method for testing the differential protection stabilty in generator? When the time of starting What will happen if differentail protection connection wrong means?

2278


When we use air circuit breaker, it has O/L protection ,time delay SC protection, Instataneous SC protection & ground fault protection. They all have some setting range. But what is the suitable/allowable setting for the above protection which will be safe for the equipment? For example-O/L protection setting have a range of (0.4,0.45,0.5,0.55,0.6,0.65,0.7,0.8,0.9,1.0)xIn Time delay SC protection have a range of (1.25,1.5,2,3,4,6,8,10,12)xIn Time delay setting is 0.02,0.1,0.2,0.3,0.4 Instataneous setting is fixed to 20xIn Gound fault setting is given 100A,300A,600A,900A,1200A This setting are for 2500A ACB. So what will be the basic allowable setting for the above protection? is there any formulae to calculate this<

2149


Difference between control junction box (cjb) and power junction box(pjb)?

4311


What is cable tray, its type, and its support?

1147