how to calculate capacitor bank value to maintain unity
power factor plz xplain with some suitable xample?
Answer Posted / shalini.b
capacitor bank value is calculated in KVAR
From Power Triangle,
KVAR = Sin(phi) * KVA
Desired Power factor = 0.96 (say)
cos(phi)=0.96
phi = cos(inv)0.96
phi= 36.86
Sin(phi)= 0.28
If the transformer rating is 1250 KVA (say)
KVAR = 0.28*1250
= 350
| Is This Answer Correct ? | 22 Yes | 8 No |
Post New Answer View All Answers
why any centrifugal blower draw more current in starting. consider id fan and fd fan?
How is the gain affected by the introduction of feedback in a control system.
How to Prepare preventive maintenance shedule of machine tool.
mccb service sittings be done?
HOW TO WORK A VFD?SAY SIMPLE METHOD
WE HAVE THE DC RECTIFIER 1500A, INPUT VOLTAGE IS 3 PHASE. HOW TO CALICULATE THE LOAD? 3 PHASE SIDE EITHER dC SIDE. PLEASE SUGGEST ME
what is the use of surge suppresser in 33 KV incoming panel. where it must be installed,inseries with incoming cable surge suppresser must be at incoming of the breaker are outgoing of the breaker
what is the operating time for LBB and how does the LBB relay realise whether cb is opened or not?
difference bewteen reverse current and alternating current
234 MVA Generator 3 phase Short circuit current Values required? Gen set Rating-234 MVA, Gen Voltage-18kv, PF;0.8, Xdv:23.5 %, Transformer Rating-18/380KV, 680MVA,Yndd1 two winding, Step up TR, ZT:35.50 %,X/R 4.33 Gen CB Position, CB open ,Disconnected open, Generator Running Voltage 18 Kv, Bi mistakes generator side earth switch Closed during that time short circuit current level in 3 Phase required, and how to test on site 234MVA Generator Short circuit current,
how meger function
What is the method for testing the differential protection stabilty in generator? When the time of starting What will happen if differentail protection connection wrong means?
When we use air circuit breaker, it has O/L protection ,time delay SC protection, Instataneous SC protection & ground fault protection. They all have some setting range. But what is the suitable/allowable setting for the above protection which will be safe for the equipment? For example-O/L protection setting have a range of (0.4,0.45,0.5,0.55,0.6,0.65,0.7,0.8,0.9,1.0)xIn Time delay SC protection have a range of (1.25,1.5,2,3,4,6,8,10,12)xIn Time delay setting is 0.02,0.1,0.2,0.3,0.4 Instataneous setting is fixed to 20xIn Gound fault setting is given 100A,300A,600A,900A,1200A This setting are for 2500A ACB. So what will be the basic allowable setting for the above protection? is there any formulae to calculate this<
Difference between control junction box (cjb) and power junction box(pjb)?
What is cable tray, its type, and its support?