If connected load of Asphalt plant is 375Kw. What suitable
KVA DG set is required. What is calculation formula. what
extra load have to consider. in what efficiency it will
work.
Answer Posted / sukhvinder
connected load=375kw
kva=kw/cos phi
kva=375kw/.8
=468.75
extra load= 20% (assume) i.e 468*20%= 93.6
total 468.75+93.6=543.68 kva say 550kva
eff. 375/550*pf (0.8)*100=85%.
| Is This Answer Correct ? | 25 Yes | 2 No |
Post New Answer View All Answers
How can I calculate per unit (KWH) fuel (Gas/ Diesel both) consumption 1MW unit?
Under wat condition statcom operates as an inductor for the transmission line?
what is the practical application of full adder circuit?
why the India electrical supply transmission loss is high when compare to us
TYPE'S OF BREKAR ,WHAT IS TRANSFORMAR & SAFTY. STARTER DOL & STAR DELTA STARTER.
why we use Test Terminal Block in 11 KV and 33 KV electrical panels.
slipring induction motor starting time Lrs operating why lrs starting time lrs outer body didn't get shock
we all know voltage is a force(emf), and the force always devides if 2 or more than2 loads are there but why does the voltage remains same is parallel, it must devide na ???
Is it advantages of having star-delta vfd than normal star vfd , if yes why?
Z transform is use when system is not a) converges b) diverges
How to address the servo drive for motor
We have studied about many techniques for finding the stability of system, ROOT LOCUS, ROUTH, BODE PLOT, POLER PLOT etc. In these which is used where. what are the difference among them... PLZ tell me.......
how does a liquid starter reduce the starting currents?
state the disadvantages of carbon filament???
A power transformer 4MVA/11KV/0.415Kv has been out of use in 12years. what maintenance actions/test need to be carried out before energizing.