If connected load of Asphalt plant is 375Kw. What suitable
KVA DG set is required. What is calculation formula. what
extra load have to consider. in what efficiency it will
work.
Answer Posted / sukhvinder
connected load=375kw
kva=kw/cos phi
kva=375kw/.8
=468.75
extra load= 20% (assume) i.e 468*20%= 93.6
total 468.75+93.6=543.68 kva say 550kva
eff. 375/550*pf (0.8)*100=85%.
| Is This Answer Correct ? | 25 Yes | 2 No |