How to test Power Transfomer vector group in the field?
Answer Posted / chicoybolanio
Put the tap position on the nominal taps.
Connect the 4 core cable with MCB on the HV side and the
leads cable at LV side and make sure that
the LV side in open circuit. Then loop together between HV
red phase and LV red phase.
Inject 415V (Switch on the MCB) at HV side and measure the
voltage at LV side for each phase. record results and by
using the test result and following proper scale draw the
vector group of the transformer winding.
Is This Answer Correct ? | 11 Yes | 1 No |
Post New Answer View All Answers
Do u know any one? how to find out in motor rated amps? formula?
Difference between drift current and diffusion current?
How to identify the start and end of 3phase 12 lead motor if U1, U2, etc numberings are lost or erased.
What is meant by celling voltage & current in excitor ?
What’s electric traction?
what happen when power factor of 2 parallely operated transformer become equle?
i have a 1500kVA transformer what is the kWH meter i need to use?
do we use links in a dc circuit?if so what s its use in it?
what is the calculation method to design core and winding of a 200kva 3phase distribution transformer?
IF TVM OF TRANSFORMER SHOWS POWER FACTOR ON 33 KV SIDE AS 0.97 LAGGING AND ON 132 KV SIDE IS 0.75 LEADING.IS THIS CORRECT.WHERE IS PROBLEM.
what is meant by rotating magnetic filed
why we take movement of rotor always in counter-clockwise direction in 3-phase induction motors?
What is the minimum distance to be maintained in between HT panel and LT panel and Instrument panel as per IEC and NEC standards?
WE ARE PLACE A NEW 75 KW MOTOR FOR JPF.IT IS CONNECTED IN M.C.C. WHEN WE ARE STARTING M.C.C.INCOMER IS TRIPPED.THEN WE ARE CONNECTED IN P.C.C WITH A MM30 RELAY PROTECTION THEN WE ARE STARTED MOTOR WILL RUN SMOOTHLY.
distribution is maximum done by a)radial b)network c) parallel d)b & c