While starting a high capacity motor, it takes 6 times the
full load current. Why it doesn't trip relay or CB's in
that network?
Answer Posted / blake_australia
The starting current for an induction motor is around 6x
full load current, however this is only for ~3cycles. Which
is about 0.06seconds (for 50Hz power).
Circuit breakers chosen for motors (D curve in Australia)
delay for more than this 0.06seconds. The curves can be
seen in any NHP breaker selection catalog. Protection
curves are more indepth than this, reading into these will
help.
Is This Answer Correct ? | 7 Yes | 0 No |
Post New Answer View All Answers
Determine the BTU size of an aircon for 20 sq metre room
I want formula to calculate current loss with distance in km.I searched many sites but didn't right answer.Plz reply me
give me a clear defination of inductance,and how can u calculate inductance of a motor
which pump used in STP
What is a feedback in control system?
In our factory so many iron pillors are exists for supporting the shed/Hangar. If do more no of earthings at one piller instead of doing more earth pits in many locations and running earth strip around the hanger, I can save the money. Please suggest this method is acceptable as per Is specifications though the Earth resitance of the farthest piller is with in the limits as per IS specifications.
What is block diagram?
In what condition the HT fuse breakes?
sir please send me previous year questions of jspl of electrical section through which i could prepare myself fpr the test.
How can we find the breaking capacity of a Load breaker switch (LBS) fed from 11 kv supply??ex:50KA, 26kA etc???detailed step vice answer pls.
what are the interview question asked in wind mill about electrical
what is vtg limit of earth and neutral at transformer side?
Single line diagrams for star to delta and DOL starters.
how synchronous condenser is used in place of synchronous generator with out negotiating IEEE standards? Can i use 3 generators as synchronous generators and 2 generators as a synchronous condensers in an IEEE 14 bus system with out disturbing the standards?
How will change the frequency in distribution side?