Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

What will be the total current for 300kva UPS if it runs on
40 to 45 percent load. Is there any formula for to
calculate the exact load.

Answer Posted / pratheesh

We can calculate the total output current of a 300kva ups.

P=&#8730;3*V*I*Cos&#934;
Where P= Output power of UPS here 300000VA
V= Output voltage of UPS ( I hope this is a 3 phase
415 volts UPS)
I= Output current. (We need to calculate)
Cos&#934;= Powerfactor of the load. Varies depends the
nature of load(Inductive, Resistive or
Capacitive. We can assume this value is as 1
because we dont know the powerfactor, nature of
load.

So I= P/(&#8730;3*V*Cos&#934;)
= 300000/(1.73*415*1)=Approximately 420A per phase(if
the load distribution is balanced on each phase)


So, If the UPS runs on 40 to 45 percent load, it will take
around 170 to 190 Amps on each phase.

Is This Answer Correct ?    14 Yes 8 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

hi frnds...pls send me aptransco previous papers .....pls..pls,,,(madhar.rocking@gmail.com)and suggest me some websites

2141


How are load losses and no-load losses measured at site in a DG set?

1758


I WANT YHE TECHNICAL AND ELECTRICAL SPECIFICATIONS OF 2x4MW 11KV 2x10MW 11KV 2x25MW 11KV 2x100MW 11KV HYDEL POWER PLANT i.e PROTECTION SYSTEM,MONITORING,CONTROL SYSTEM,GENERATION,SYNCHRONISATION,METERING PLEASE SEND THE DETAILS TO MY MAIL ID SPRAVEEN_222@YAHOO.CO.IN

2098


with 3 phase board on a 63 amp rcd is it ok to have 6 electrical showers 2 on each phase and what problems could happen

1829


i have flexible wire. size of conductors is 0.190 mm & no.of conductors are 48. then size of wire comes 1.37 sqmm instead of 1.5 sqmm . the what is tolerance for this size.

1798


How eddy current generation support the idea of train braking?

2011


What are the effects of electrical faults?

1040


difrent between vcb acb sf6 and mccb breakers

5449


What should be the values of settling time, peak time, steady state error, overshoot, rise time, MPOS (Maximum percent over shoot) to keep the system in transient state, to keep the system in steady state ?

2264


In convertor can we use rectifier thyristor in place of invertor thyristor with explain.

1824


what is booster? and how it is connected in a circuit?

2631


Explain Even and Odd signals?

1922


excitation limit of an excitor

2064


in a silicon diode we can measure .7v in a voltmeter.but why we can't use this voltage for using?

1929


which type of effect of turbine and generator reverse power protection ?

4197