for 12KW motor which cable size has to select for ex.10
meter.
Answer Posted / prodip das
1. we have to select cable
for that first calculate current=12X1000/1.73x400x.95
=19 Amps
Type of cables= single core NYY(Red/Yellow/Blue/Green)
Cable size3x1CNYY
NYY 2.5 sq.mm
(ccc)=19.61A
Group rating=.68
sand bed=.90
Rating factor=.68x.90=.61
Actual CCC OF 2.5SQ.MM CABLE
=19.6X.61=11.96A
=26.20x.61=15.98
=33.63x.61=20.5143(OK)6 sq.mm
Votlage drop as per IEE regulation
Distance=10m(more)
=5.9x10x.152=8.968V(ok)
Finally SWG=6sq.mm
| Is This Answer Correct ? | 7 Yes | 3 No |
Post New Answer View All Answers
I Have 3 Phase 10 KW AC Alternator i found one phase weak, so what will be the reason & what action shouls i take to rectify the same.
are there rmu for 3 transformer?
What is George phenomena to start the synchronus machine?
how the works electronic energy meter?
what is difference between line differential and transformer differential?
Why the output of OP-AMP is always less than Vcc?
Is it required to lay 2 runs of GI wires along with armoured cables from one power DB to another Power DB?
what is the advantages of having in-built acvvvf (without seperate inverter in the control panel)in the drive system of elevators?
defination of lines
which network topology offers the greatest level of tolerance?
ROC converges if pole and zero lies inside a) origin b) z=1 c) pole d) zero ? Explanation please? if ROC does not converges then?
what are the types of electromagnetic forces developed in practical transformer?
Explain marx circuit.
How phase displacement change in the over current relay coils.
what is the safety points of vaccum circuit breaker.