for 12KW motor which cable size has to select for ex.10
meter.
Answer Posted / prodip das
1. we have to select cable
for that first calculate current=12X1000/1.73x400x.95
=19 Amps
Type of cables= single core NYY(Red/Yellow/Blue/Green)
Cable size3x1CNYY
NYY 2.5 sq.mm
(ccc)=19.61A
Group rating=.68
sand bed=.90
Rating factor=.68x.90=.61
Actual CCC OF 2.5SQ.MM CABLE
=19.6X.61=11.96A
=26.20x.61=15.98
=33.63x.61=20.5143(OK)6 sq.mm
Votlage drop as per IEE regulation
Distance=10m(more)
=5.9x10x.152=8.968V(ok)
Finally SWG=6sq.mm
Is This Answer Correct ? | 7 Yes | 3 No |
Post New Answer View All Answers
How to calculate the heat load for a electrical room
When we use 3 terminal resistor?
plz tell me,ht and lt panel terminals in substations explain beiefly
difference between main metering kiosk and check metering kiosk
HOW TO WRITE A QUENTION ANSWER? I MEAN SHORT OR LENGHTHY ? OR FROM THE BOOK AS BOOK..... SOME TIME WE GIVE A ANS FROM THE BOOK AS LIKE BOOK ND WE GET MINIMUM 60% MARKS OR MORE THEN....... THEN HOW TO FILL THE Q-PAPER?
Enlist four components of electrive drives.
Can anybody please refer the best and simple book for about Protection relays and in detail of all its protection ?
is there any role of power factor with frequency variation? and how we can manage the frequency variation?
exolain the star delta connection
what are the difference between AC lamp and DC lamp
use of choke in APFC panels
WHAT IS THE WORKING PRINCIPLE OF A GENERATER.how is a GTG (Gas TURBANE Generater) working.plz explane
why current is constant on d.c?
why normally Generator rating are between 11Kv to 22Kv?
Comparision of Air break circuit breaker, SF6 Circuit breaker and vacuum circuit breaker.