how we can calculate which capacity capacitor bank we have
to add for improve pf?
Answer Posted / abdulsubur
p total connect load in kw =932
cos 1 =power factor before improvement =0.8 assume
cos 2= poer factor after improvement =0.9
kvar 1= ptan1 932*0.75=699.03kvar
kvar 2=ptan2 932*.4843=451.39kvar
req rating of capacitor bank =kvar1-kvar2
=699.03-451.39
=247.64kvar =250kvar
Is This Answer Correct ? | 12 Yes | 4 No |
Post New Answer View All Answers
can the measured percentage error during calibration of single phase energy meter be negative?
Formulae for calculating the transmission line losses for different voltage levels
harmonics filter
Please brief what is sinewave
is IS says that neutral should be brought to switch box. and this one is a recomended practice
how can i get an electrical c-certificate?
What is pole of the system?
How one can check the MAIN of a house wiring ?
What is the effect of interchanging core(made of steel) and winding(made of copper) material in case of transformer? Give proper explanation in regard to different losses in transformer.
Dear Brother can u tell the proper size selection of cable & the fault level calculation of braker, busbar etc. pls mail me at azeemk30@gmail.com
How can we calculate the efficiency of a Running (On-Load) Motor ? What parameters are required and what is the method ?
What is force on a conductor in a magnetic field ?
why do motors burn out? I understand why adding parallel loads to a power source means more current moves through the circuit, and can destroy circuit elements by overheating. What about when you have a vaccuum cleaner intake flush against a floor, a room fan sitting directly against a wall, or a power drill trying to drill through something too hard?
What is earth system using on the floater TN-S or TT. Iam not sure and what ICCP
The transmission does not have options: a)Partition noise b) Flicker noise c) resistance d) Short noise and reason