hi this is noor in my work spot, i arranged THERMOCOUPLE in
the place of RTD. (in FEED WATER tank). can i use T/C or not?
Answer Posted / manash ranjan jena
For feed water service the process temp. is always below
300 Deg. C. So you can very much use a RTD. And in lower
range RTD is a better solution than T/C. As it has a linear
curve and no compensation required. And even the accuracy
of RTD is better than T/C. However you can very much use a
T/C if the control network allows.
| Is This Answer Correct ? | 12 Yes | 0 No |
Post New Answer View All Answers
Is it ok, to use non-contact type Radar type LT, on a tank that is half circular from the bottom side? If yes the, isn't the waves gonna bent in other directions?
how can i calibrate the temperatuture gauge used by temperature bath(dry block) i mean step by step procedure?
principle of automatic votage regulator
What is the Working principle of Dozing valve?
what is difference between HOT permit and cold permit
can you send remote seal interface level transmitter calculation steps for oil water saperator.
what is the different between deflection type measurement and null type measurement in RTD?
what is diffrance between FF & SMART, explain with difination
What are the interlocks we have to check during the start up of LP/HP compressor?
What is the purpose of the analyzer in petrochemical plant?
what are the definitions of input, output, command & signal according to instruments controlled by PLC using DCS System?
Explain the working principle of lvdt?
What is the diffrence between digital signal processing and discrete signal processing?
How you calibrate absolute pressure with the calibration range of 0 to 1000 0C Absolute. Please explain the procedure for calibration.
hello sir/madam, I,Subramanian need 5yrs placement papers of officer trainee of Instrumentation technology.pls send to this mail id mani_nxtgen@yahoo.co.in please do the needful. with regards, subramanian.v