three phase 180kva diesel generator can take how much load
in amp and what is formula to get this?
Answer Posted / santosh jagale.
Generator rating is 180KVA.
Actually all electrical data is made avialable on genrator
name plate by manufacturer.
If you consider the PF is 0.8 Lag.
Then KW=KVA*PF
i.e. KW=180*0.8
=144 KW
P(KW)= 1.732*V*I*PF
Then,
144=1.732*415*I*0.8
I= (144/1.732*415*0.8)*1000
I= 250.42 Amps.
This is the full load current of generator with 0.8 PF &
415V.
In case of DG sets the generator O/P power is restricted by
power of driving engine, beyond that limit you can,t load
the particular generator. You can put upto 125% of to
genrator but not for too long period.
| Is This Answer Correct ? | 52 Yes | 4 No |
Post New Answer View All Answers
What is the BS(British Standard)code for 11kv motor
how to calculate power consumption in slip ring motor at different step
how we provide neutral earth on synchronising panel as per electrical standards?
Can I use star delta connected induction motor for dual supply voltage?
what is the affect of earth's magnetic field on the frequency used in aircraft???
What is the drawback of class b amplifier? How is this minimized?
What id difference between power and energy?
What happened ,If 3 phase clearance not maintained in 33KV Line,11KV LIne etc?
Two bulbs of 100w and 40w respectively connected in series across a 230v supply which bulb will glow bright and why?
for what voltage will reactive power be largest in 380 kv line : a) 375kv b)380kv c)385kv
what is dry and wet frequency withstand voltage? why & where it is used??
Explain the functioning of diode?
What aturn on methods of scr?
main difference between ac and dc?
How to calculate mf when meter equipment and meter are connected