calibration of instruments.

Answer Posted / raffi

Calibration procedure:
calibration equipment: calibrator with handpump
For ex: Range of Transmitter is 0-100psi

Step1: connect the calibrator to the transmitter
Step2: connect the multimeter in series with transmitter to
verify the transmitter o/p in mA
step2: Apply the pressure to the transmitter by hand pump
in calibrator
Step3: compare whether both calibrator and the transmitter
showing the same value.if you applied 50 psi throuhg the
calibrator then the transmitter should have to show the
same value.If you find any error.Do the zero/span
Adjustment.by adjusting the zero/span screw
increasing/decreasing
step4: compare the transmitter and calibrator as per follows

calibrator Transmitter Transmitter o/p
in psi in psi in mA
0 0 4
25 25 8
50 50 12
75 75 16
100 100 20

Is This Answer Correct ?    22 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how to design orifice plate?what is the equation?

1710


Which is the best field foundation bus. ( FF ) Yokogawa, Honeywell or others ?

1459


what different types of problems do occur while doing instrumentation commisioning and how to solve them? please explain in detail

1403


how to check earthing,what is minum ohms for proper earthing

1597


What is shielding effect?

1865






May I have a brief note above the voltage barriers? Whats is the purpose? Please mail me if you've operational details, mail id: rajkumar.diice@gmail.com

1731


what are the diff. in servo and regulatory control?

3582


i am preparing for BARC ,so plz mail me how to prepare for BARC. ALSO IF POSIBLE SOME RELATED QUESTIONS. MY MAIL ID IS khushi_4uall2003@yahoo.co.in

2663


If a control valve is hunting means means if we are giving 50% to the cv, the cv will open at 51% then slowly slwoly it will reaches 49% , so what to do for solve this problem. The cv is double acting and mounted for anti surge operation, it having 4 nos. volume booster, one sov, one positioner, etc..?

1756


how to measure oxygen which methods are using?

1563


Explain why use mmwc unit?

720


How to calibrate radar type level transmitter for interface level? Total liquid(liq.1 and liq.2), level both the liq individually? For. Both the liquid levels how the signal will go from transmitter to dcs? How to calibrate. Single radar 9:26:55 AM for 2 different liquids in a tank?

1688


Full form of KKS when use DCS.

2777


what is the procedure of O2 sensor(ABB) calibration?

1830


What are the type of bonnets in the control valves?

1502