What is the formula for calculating Transformer Losses &
Efficiency. I want to compare the Transformer efficiency at
different loading condition.
Answer Posted / kashifhabib
Efficiency = (Output/Input)*100
&
Output (KW)= KVA * Power Factor
Input = Output + Iron losses + Copper losses
Iron losses are due to Primary voltage so remains constant
can be calculated by open circuit test
Copper losses are due to secondary current I*I*R
can be calculated by short circuit test
Exp: Full load copper losses 800 W
1/2 load copper losses will be 200 watts
| Is This Answer Correct ? | 368 Yes | 101 No |
Post New Answer View All Answers
11 kg trivevter meter has rating of -/5amps. And pt ratio11000/110v and is connected with 11kv ct/pt unit of cr ratio 75/5amps. And pt ratio of 11000/110v while checking accuracy of meter with HT Accuchek meter what value of PT ratio and CT ratio to be filled in Accuchek meter
how to decide no of electrodes for 1600A LT Main incomer panel
What is the lifetime of a Thyristor? Is there a recommended lifetime for thyristors after which they should be replaced?
How can you calculate the size of the down conductor cable for the lightning protection system. Is 70mm2 cable can replace 95mm 2 bare copper cable when the copper tape size is 25Wx3 thk mm.
What will be result if we connect LT votage to the terminal of HT motor?
what is RFID? thire application;
how single phase preventer works ?
any body,pls tell me how to done relay coordination ? how to coordinate by TCC curve?how to read the tcc curve?
which type of cabel
Is it required to use Automatic transfer Switch in L&T panel board if we use AMF panel with DG set? How the single line diagram will be? Please forward the material to sreenu_207@yahoo.co.in
Match the following a)(X'+Y') b)X'Y' C)XY 1)NAND 2)NOR 3)Carry
why we setting 95 deg and 105 deg in wti and oti of distibution transformer ? give the reson for that ?
The size and construction of bushings in a transformer depend upon?
What is the difference between PS & metering CT (5p20,0.5 etc.)? Why in PS class CT only Vk is given ? Is PS class CT is more accurate than metering CT?