1.what to do if ferquency of any power system continue to
decrease ?
Answer Posted / sanju
u can bring the frequency to normal by decreasing the laod
shared by the generators. But i dont think any power system
engineer can afford to loose laod. The frequency can be
brought back to the noraml valsue after the following:-
1.make sure that the governor sets of all generators are
working fine.
2.make sure that that the droop characterstics of all the
governors connected are same.
3.make sure that there is no problem with prime mover side.
i hope this wl solve ur problem
sanjeev
| Is This Answer Correct ? | 10 Yes | 1 No |
Post New Answer View All Answers
If Neutral Grounding Resistor (GR) failed/shorted. Is it repairable.
Dear sir, In our plant have Station Transformer having capacity,i want to know, why LV side 40 - 40MVA is given? & how we can get 6.3 KV supply from tertiary(i.e. Open delta connection), Vector Group YNyn0 - yn0 +d MVA Rating 80MVA / 40 - 40MVA + 26.7MVA Voltage rating 420 (Tap range +6,to -10)81.25% /11.5KV - 11.5KV +6.3KV
A 15 kw squirrel cage motor having a maximum efficiency of 90% on a continuous full load has temperature rise of 42 degrees celcius after 30 min and 52 degrees celcius after 1 hr under the above operation conditions. a) calculate its final steady state temperature rise on continuous load and the heating time constatnt. b) if the motor is operated on a short load for 9 min estimate its temperature rise. c) calculate the maximum overload that can be applied on a short, 9 min rating so that the temperature rise is the same as the final steady state temperature rise on continuous load.
1.4 What is meant by CT knee point voltage and how would you determine it
what are the analog quality input for protection function?what are minimum reqiments?
Explain the working of variable frequency transformer?
i have attended the interview on 4th June,08 at Kolkata in IOCL, can anybody tell me what is its result
I am going to appear RRB Sr. Section Engineer Exam, Electrical. Can you send me previous year questions of RRB Electrical engineer. specially Section Engineer questions. my email id is likerahulworld@gmail.com
In EHV transmission line a neutral grounding reactor is often placed at neutral point of shunt reactors. What is the recommended protection for this neutral grounding reactor? Should I use a fast closing switch to bypass neutral grounding reactor when this protection operates?
Draw transformer phasor diagram.(full load,no load)
how we decide wire gauge for ac or dc coil and what is the basic diff. B/w these two coil?
What will be the diameter of pipe between conservation tank and transformer
What is magneto on a gas generator. how it functions. its out put is d.c or a.c. how it can be checked for correct functioning
i want bhel placement paper for electrical if anybody having pl send to my id kavitha867@myway.com immediately
how to changeover ups in this power failur time?