If the capacitor bank is installed in switchyard say
132/22kv then on LT side say 22kv/0.433kv is it necessary to
install capacitor bank for maintaining power factor. if pf
is maintained on HT side then will that be maintained on LT
side as well.if not then how&why??????/ please
explain...........
Answer Posted / zahid noor
If capacitor bank is installed in switchyard & capacitors
are connected on HT side , it will try to balance losses of
transmission line and not towards LT side, where as for
maintaining /increasing LT side voltage, we need to install
seperate capacitors nearer to load so as to maintain PF at
LT side also depending upon connected load & distance of
equipment connected in LT side.
| Is This Answer Correct ? | 12 Yes | 0 No |
Post New Answer View All Answers
what are the usual topology of transformers at different substations in the power system and why that particular topology is choosen. what are the limitaions of that topology?
what's the requirement of Dy11d0 connection of 3 phase transformer?what's use of it?
What is industrial plc
hi friends if you have any 400KV Substation Erection and installations Drgs please send to me.My email id:kandi.suresh441@gmail.com
WHaT IS THE CONCEPT OF INDUCTION LAMPS IN MODERN LIGHTINGS, and HOW IT WORKS TO EMIT LIGHT ( AS NO ELECTRODES ARE PRESENT ) ?" COULD INDUCTION LAMPS CAUSE INTERFERENCE WITH COMUNICATIONS INTO A STORE USING INDUCTION LIGHTING ? WHAT IS THE BENEFIT OF USING THE LOW FREQENCY INDUCTION LAMP , VERSUS LED , AND VERSUS FLUORESCENT, AND VERSUS ANOTHER KIND OF LIGHTING . THANK yOU MOISES GUINDI
what is the common earth
any one guide me to reduce the power factor of diesel Generator from 0.97 Leg to 0.8 Leg.with out any change in my load.
I have a CT meter with ratio 60/5. The meter reading of previous month was 3290.49 and that of current month was 3797.26. How many chargeable units as per normal meter should be my reading.
why in a swquence network representation, the negetive sequence generated voltage is taken as zero?
What is the function of capacitor in electrical circuits?
Control cables in S's will carry 1000v which is AC R DC? Pls answer meĀ
How do you calculate the actual power consumption of an inductive load appliance. Say, a deep freezer of 200watts
why ct's&pt'S out put called as burden,why compelsary short ckt the secondary of ct's while removing the burden?
In which of the following case, the rotating magnetic field is reversed? A regenerative breaking B plugging C dynamic breaking D forward motoring
how to calculate transformer turn primary & secondary side 11kv to 420v