6 MVA transformer secondary is rated for 725V at no load.
The incommer ACB is rated at 690 V, 3200 Amp. Would there
be any effect on performance of ACB due to lower voltage
rating?

Answer Posted / rvg

The transformer details shows no load voltage and we can
assume about 3-4% decrease with full load. ACB with rated
voltage 690 should not be suitable for 725V. ACB's nominal
voltage should be 1.414 time the applied voltage.

Is This Answer Correct ?    6 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How does a transformer contribute towards the widespread popularity of ac system over dc?

794


how to i get B licence,i am completed BE electircal and electronics engineering.i want to konw the proceduure to get b licence

1331


What is T’Q and X’Q and X’D ? and what is saturated as well as unsaturated ?

1420


What will be the voltage impact on secondary side of two transformers with different vector groups when both voltages are compared.

1681


What is dielectric loss?

784






Differentiate between induced emf and self inductance?

748


whether starting current is limited to rated current of motor through soft starting or it exceeds the rated current?

1197


Do inductive loads have distorted current waveforms ?

1520


What is the angle of inclination for the oil connection from transformer conservator to Bucholz relay and why?

1827


fuel-air ratio in a petrol engine fitted with suction carburettor,operating with dirty air filter as compared to clean filter will be

769


Draw a circuit diagram in which if button is open we can use socket and bulb as a series test circit and if button is close than simple we can use socket as any load purpose.

1568


State thevenin’s theorem?

771


DEAR SIR/MADAM,CLEARLY EXPLAIN ABOUT CRAWLING AND COGGING EFFECTS IN INDUCTION MOTOR.

1566


condition Autotrip facia come on control panel of electrical transmission line?

1228


How vfd saving power.

1708