6 MVA transformer secondary is rated for 725V at no load.
The incommer ACB is rated at 690 V, 3200 Amp. Would there
be any effect on performance of ACB due to lower voltage
rating?
Answer Posted / rvg
The transformer details shows no load voltage and we can
assume about 3-4% decrease with full load. ACB with rated
voltage 690 should not be suitable for 725V. ACB's nominal
voltage should be 1.414 time the applied voltage.
Is This Answer Correct ? | 6 Yes | 2 No |
Post New Answer View All Answers
How does a transformer contribute towards the widespread popularity of ac system over dc?
how to i get B licence,i am completed BE electircal and electronics engineering.i want to konw the proceduure to get b licence
What is T’Q and X’Q and X’D ? and what is saturated as well as unsaturated ?
What will be the voltage impact on secondary side of two transformers with different vector groups when both voltages are compared.
What is dielectric loss?
Differentiate between induced emf and self inductance?
whether starting current is limited to rated current of motor through soft starting or it exceeds the rated current?
Do inductive loads have distorted current waveforms ?
What is the angle of inclination for the oil connection from transformer conservator to Bucholz relay and why?
fuel-air ratio in a petrol engine fitted with suction carburettor,operating with dirty air filter as compared to clean filter will be
Draw a circuit diagram in which if button is open we can use socket and bulb as a series test circit and if button is close than simple we can use socket as any load purpose.
State thevenin’s theorem?
DEAR SIR/MADAM,CLEARLY EXPLAIN ABOUT CRAWLING AND COGGING EFFECTS IN INDUCTION MOTOR.
condition Autotrip facia come on control panel of electrical transmission line?
How vfd saving power.