6 MVA transformer secondary is rated for 725V at no load.
The incommer ACB is rated at 690 V, 3200 Amp. Would there
be any effect on performance of ACB due to lower voltage
rating?
Answer Posted / rvg
The transformer details shows no load voltage and we can
assume about 3-4% decrease with full load. ACB with rated
voltage 690 should not be suitable for 725V. ACB's nominal
voltage should be 1.414 time the applied voltage.
| Is This Answer Correct ? | 6 Yes | 2 No |
Post New Answer View All Answers
what are all types of cross section in AC cables?
Why slip ring ind. motor power consumption is low compare to induction motor .same 90 kw motor used same load output
which are the criterias needed to select the kind of neutral earthing(solid earthing,resistance earthing,etc.) at various voltage levels in electrical distribution?
why servomotor motor? where i apply for best output?
For a three phase induction motor, what will be the effect on motor if the neutral of the system is shifted to say 20 deg.?
What do you mean by passive circuit elements and why these are called passive?
Sir pl provide 5 year sample paper for post junior engineer(electrical).I have currently applied for junior engineer (electrical) on RRB Ajmer
Why the power factor improvement is so important in industrial loads
why transformer tank is in rectangular shape what happen when it is in step shape
how to find number of run cable laying[LT side] for transformer & alternator secondary side? [above condition for getting output power transformer to main panel side] give the example.
What is conventional thermal current (Ith)
What Maximam Gap Taibaar & Bush
what is the main difference between power devices and signal devices
If we have use two power cable for incomer, that time how many use cbct for earth leakage protection? 1 or 2 if 1 way? If 2 way?
Difference between megger test equipment and contact resistance meter test instruments?