why is the vector group analysis done in transformer tests

Answer Posted / joe callaghan

Transformer vector relationship is tested by shorting the
primary A phase to secondary A phase, then applyying a
three phase voltage to the primary side of the transformer.
Voltage measurements are then taken as follows:

A-B
B-C
C-A
B-b
C-b
B-c
C-c

These values will then allow you to draw the vector diagram
of the transformer.

Is This Answer Correct ?    32 Yes 9 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how electrical earthing maintenance done in industry?

1040


is that any software calculator to calculate the size of cable

1870


what are symmetrical and non symmetrical components in electrical installation.

1614


how to calculate the tarriff for an industry whose kva demand is 10 mva

1519


What is the RME and explain the full form and what is the RME work?

2123






What the formula for calculating no.of earthings & size of earth strip for 100mX90m shop.

1888


How to decide the size of the capacitor for a single phase induction motor say 2 HP ??

1653


What will happen if we on 200kvr capacitor bank(11kv in bus)If there is low load on transformer (1.5 mva 33/11 kv)

1128


Define conversion efficiency of a power amplifier.

703


What are the necessary components of the feedback control system?

733


defult setting in p220 micom motor proction relay for 11kv,640kw,f.l.a.-40a,1440rpm ht motor?

3226


In India the supply voltage is 230 volt A.C. During the negative half cycle phase becomes neutral and neutral become phase? or what will happen during negative half cycle? how the electrons flow during positive and negative half cycle?

1503


Explain about how is it working Earth fault'relay and wahts the resistance value of earth bed

1035


The principle of switching circuits for different types of batteries in application of storage systems

1533


Percentage losses in power generation?

2502