Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how to tune the closed pid loop?

Answer Posted / welcome4ujd

Controller Tuning

If the controller is withdrawn from the control panel face,
further adjustments are available which are used to tune
the controller to the process.

When a control loop is commissioned, the controller
settings are adjusted to correspond to those, which have
been specified during the design of the control system. If
a large section of process is to be commissioned; possibly
a mathematical model of the process will have been
developed from which the optimum controller settings can be
calculated for efficient and stable operation. It is these
values which are set into the controller before start-up
and, if calculated correctly, no further adjustment will
be required.

In some cases it will be necessary to tune a controller
without having the benefit of knowing what the settings
should be. It must always be remembered that the
adjustments cover a very wide range of sensitivity and
response. If adjusted haphazardly, the process may shut
down and damage to equipment and lost production may occur.

The task of controller tuning is usually left to an
instrument technician with experience in the cause and
effect of process reaction and controller adjustments.

There are many trial and error methods of controller tuning
which do not involve mathematical analysis and should be
demonstrated by an experienced person, otherwise shutdowns
may occur.

The first adjustment, which would normally be made, would
be to set forward or reverse action as required. A forward
acting controller has increasing output in response to an
increasing measured variable. A reverse acting controller
has decreasing output in response to an increasing measured
variable.
Empirical Tuning Method
Proportional only controller

- With transfer switch at manua1, set PB at maximum
or at safe high value, usually 200% PB.
- Move transfer switch to auto and make changes in
set point. The time required for the disturbance to settle
may then be noted.
- Continue reducing band-width to half its previous
value until the oscillation do not die away, But continue
to be perceptible.
- Now increase the band-width to twice its value.
This gives the required stability, that is, the minimum
stabilising time and minimum offset.

Proportional plus integral action

- Set the Integral Action Time (IAT) to maximum.
- Adjust the proportional band as for a proportional
controller.
- Decrease the IAT in steps, each step being such
that line IAT 1s halved at each adjustment. Below some
critical value, depending upon the lag characteristics of
the process, hunting will occur. This hunting Indicates
that the IAT has been reduced too far.
- Now increase the time to approximately twice this
value to restore the desired stability.

Proportional plus derivative action

- Adjust the Derivative Action Time (DAT) to its
minimum value.
- Adjust the proportional band as described for
proportional controller, but do not increase the band when
hunting occurs.

- Increase the DAT (that is, double each setting) so
that; the hunting caused by the narrow band is eliminated.

- Continue to narrow the band and again increase the
DAT until the hunting is eliminated.
- Repeat previous step until further increase of the
derivative action time fails to eliminate the hunting
introduced by the reduction of the proportional band, or
tends to increase it. This establishes the optimum value
of the DAT and the hunting should be eliminated by
increasing the width of the proportional band slightly.


Proportional plus integral plus derivative action

- Set IAT to a maximum.
- Set DAT to a minimum.
- Adjust the proportional band as for a P + D
controller.
- Adjust derivative using same procedure as for
above, P + D.
- Adjust integral to a related value of the final
derivative setting.

A three-term controller is therefore adjusted as for a P +
D controller and the integral value simply related to the
derivative value.

In many cases, the setting procedure may be shortened by
omitting settings, which are outside the probable range.

The process should then respond to set point or load
changes, where integral action removes offset and the
second overshoot of set point is approximately 1/4 the
amplitude of the first. This is commonly referred to as
the 1/4 decay method and is generally agreed to be the
optimum controller setting for a P + I controller.

The above method is only used when no other controller
setting data is available and must be practised with care.



Optimum Settings (Ultimate Method)

The closed loop or ultimate method involves finding the
point where the system becomes unstable and using this as a
basis to calculate the optimum settings.

The following steps may be used to determine ultimate PB
and period:

1. Switch the controller to automatic.
2. Turn off all integral and derivative action.
3. Set the proportional band to high value and reduce
this value to the point where the system becomes unstable
and oscillates with constant amplitude. Sometimes a small
step change is required to force the system into its
unstable mode. The below figure showing typical response
obtained when determining ultimate proportional band and
ultimate period time.
4. The proportional band that required causing
continuous oscillation is the ultimate value Bu.
5. The ultimate periodic time is Pu.
6. From these two values the optimum setting can be
calculated.





• For proportional action only

PB% = 2 Bu %

• Proportional + Integral

PB% = 2.2 Bu %
Integral action time = Pu / 1.2 minutes/repeat

• Proportional + Integral + Derivative

PB%=1.67Bu
Integral action time = Pu / 2 minutes/repeat
Derivative action = Pu / 8 minutes

Example 1
When a step change was applied to a closed loop system with
a PB% of 14% sustained oscillation of the output was
observed. The time between two adjacent peaks was measured
as 1.2 minutes. Calculate the optimum setting for a P only
& P+I+D system.
[(28%) & (23.38%, 0.6 min/rep, 0.15 min)].

Example 2
A closed loop control system is found to oscillate when the
proportional band is reduced to 23%. A trace on a chart
gives a measurement of 6 mm between adjacent peaks. If the
chart speed of the recorder is 10mm per minute, calculate
the optimum controller settings for P+I+D control.

(38.41%, 0.3 min/rep, 0.08 min)

Is This Answer Correct ?    4 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

steps for installing orifice plate?

1854


what is different between 2,3&4 wire rtd and how much maximum distance using plc to field.

2781


What are continuances of connecting earthing and shield of branch cables (instrument to Junction box), at the same earthing pot provided on JB? Is it ok, or may produce some problem? 

2500


The Design Calculation of Level Transmitter For Different Structure open & Closed Vessel, Eg. Diff. Level Tx., Capacitance For Continous Operation

2860


Draw a complete P&ID of a flow suction tank indicating all control & protection equipment. Indicate all its inlets and outlets. Explain the controls for this system

1534


how the arrangement of equipments done in control room

2003


i have been asked by QAFCO to appear for interview for thy post of Instrument Designer(INTOOLS)..i m engineering graduate with 5 years exp. in design engineering.Will this job profile suit me??i need all ur help n suggestions for thy same?

2231


Why plc require in analog input 4-20amp & 0-10 volt?

1143


I have a Control VAlve having size of 2 ".Only the known parameter is Pressure drop . Its 2 Kg. Then How to calculate control valve sizing means Cv.

2355


What you mean by multi stage control vavles?

1813


What is the difference between PLC and DDC?

2189


What is Predictive Maintenance

1174


Q1: Consider part of a control loop, which excludes the transmitter, consisting of a process, a controller and a control valve which may be represented by two dead times of 0.5 min each and three exponential lags of 0.8 min., 1.0 min. and 1.5 min. respectively. We wish to express this system as an overall first order plus dead time (FOPLD) model ie gain, time constant and process dead time. (We will see later that this is often done, to simplify controller tuning). For this exercise, gain is considered to be 1.0. (A) If the transmitter is a flow transmitter whose behaviour can be described by a dead time of 0.2 min. and an exponential lag of 0.5 min. in terms of the overall dead time and overall first order lag how can the system behaviour be approximated ? Overall dead time = Overall time constant = (B) If the transmitter is a temperature transmitter with a temperature sensor in a protecting well whose behaviour can be described by a dead time of 0.7 min. and an exponential lag of 15 min. how can the overall system behaviour be approximated now? Overall dead time = Overall time constant =

1950


i want to know the interview format fot gail, instrumentation. pls answer me in habib.sami1003@gmail.com

3180


May I have a brief note above the voltage barriers? Whats is the purpose? Please mail me if you've operational details, mail id: rajkumar.diice@gmail.com

2140