I have installed capacitor bank at secondary transformer.
cos phi is increase. but on load (far from transormer), it
still poor. Can anybody explain it??
Answer Posted / jinu
capacitor bank will improve the power factor towards the
supply side only. ie if you are measuring the power factor
before the capacitor bank it will show the improved power
factor. But the same time when you measure it after the
bank it will show you the load power factor not the
improved power factor.
| Is This Answer Correct ? | 19 Yes | 0 No |
Post New Answer View All Answers
What are the factors which influence the choice of specific magnetic and electric loadings of a synchronous machine?
how to select fuse rating for a 3-phase motor ???
What is difference between unity power factor wattmeter and upper power factor wattmeter? In short circuit test of transformer the wattmeter used is unity power factor type or upper power factor type wattmeter?
what happen ehen synchronisation is done at below rated speed
Explain about 3 phase motor fault current calculation with examples?
How many VSC based HVDC are there in India and the world
What are the Formula of computing Back up Time of 500kVA UPS with 4 Battery Banks, each bank composed of 43 pcs of Batteries 12V150Ah. How to compute the Back up Time of UPS? We have also 3X500kVA UPS running in Parallel same composition as I write above.
advantage and disadvantage of team work?
I NEED RRB APTITUDE QUESTIONS AND MODEL PAPER,PLEASE SEND MY E-MAIL joo28_eee@yahoo.co.in
what will happen if OLR CT in all phases are short circuted
Will any motor burn if voltage provided is lesser than the rated voltage???? If yes, then how is speed control possible with voltage control
What is block diagram?
why the name trunking bus PT
Details about Flux Compensated magnetic Amplifer starter for motors
Why the efficiency of generator is more than motor in swinburne's test