if 20 hp motor starts directly stars and contenious run .
what will be the effect.

Answer Posted / nishant

For staring of Motor above 5 HP we need a starter with
overload protection e.g. Star-Delta Starter and D.O.L.
Starter for limiting starting current as motor takes 5-7
times of its full load current during starting So if we
start 20 HP motor Directly the line fuses will Blown Off
due to high starting current.

Is This Answer Correct ?    19 Yes 6 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Why does amplifier gain reduce?

649


HOW CAN I GET 5CORE HO7 CABLE SIZE IF I HAVE 1800A?

1624


what is cathodic protection and why it use in industries?

1757


How to design a Unit auxiliary transformer for a power house having a unit of 65 MW and Generating voltage of 11 KV and Secondary voltage of 433V

1668


List the disadvantages of constant k filters?

1081






Why reactive power is needed in a power system? How is it being absorbed or delivered by alternators? For reactive power control we are changing excitation but reactive power absorbing or delivering related to stator. How these two are interlinked? i want a detailed explanation with necessary expressions and figures?

1405


Why does the rotor rotate?

1815


how do we calculate length of starting time and repeated starting of a direct online starter?

1554


what is the eight bit unit?

1975


On a 3 winding transformer YNynd11, how do you apply REF protection to the Delta tertiary winding that is supplying auxiliaries to a substation?

3612


would the same effect be achieved by reversing the connection to one winding of the induction motor 3-phase?

1338


What is EMC filter in VVVF Drive ?

2135


what is allowed value of zero sequence impedancce of 6.6 kv nuetral earthing transformer ?what is the actual value

1661


For overhead protection we use which transformer?

1949


Usually in the L & T make MCC feeders' power circuit,we have BMR after the MAIN CONTACTOR.,can we interchange their position, keeping the control logic same???

1642