Answer Posted / venkat iyer
Selection of CTs depends upon its usage, whether for
metering or protection. Class of accuracy, VA burden and
palatability to instrument safety factors need to be
considered incase of metering CTs. In case of protection
CTs, linearity factor w.r.t its primary current and
accuracy factors need to be considered. Metering CTs are
expressed in terms of Class 1 or Class 3 where as
protection cts are expressed as 5P10 or 5P15 or 5P20 or
10P10 etc. The first digit stands for the class of accuracy
and P stands for protection and the last two digits stands
for linearity.
| Is This Answer Correct ? | 44 Yes | 0 No |
Post New Answer View All Answers
what are the tests comes under the type test, what tests comes under routine tests.
what is mathed of check the D.C MOTOR 181 KW (ARMATURE AND FIELD) WHAT IS THE MATHED OF CHECK THE THYRISTOR MODULE (HIGH CURRENT)
1600kva capacity Transformers how the bucholz relay,Oil temperature,winding,surge relay relays setting are to be done
1. What is maximum permissible distance between smoke detectors ? 2. How do we decide number of smoke detectors required in a large office, warehouse, hall etc ? 3. What should be maximum height of smoke detectors ? 4. Where do we use heat detector, optical smoke detector, temperature sensitive detector ?
Percentage losses in power generation?
Why in 6 KV XLPE cable termination kit used and why not in 380 V xlpe cable same is not used
All the socket in a room become very hot, the Wall was also became very hot and the earth conductor also became live, what in your view might be the possible causes?
what is the difference between megger and earth resister ??
Why the frequency of ac in india is 50 hz but in some other countries it is 60 hz.
HI....HOW CAN BE MESARED THE VALVE OF NEUTRAL GROUND RESISTOR WHIC IS LOCATED AT SWICHGEAR ON GENERATOR SIDE....
Define filter?
where the lexical paramater will use in fron end?
What is the use of oil in transformers?
by what factor the starting current is used when comparing star and delta connection for motor starting?
Is it possible to obtain 480v or 550v in single phase output by giving the input to 230v to a single phase torodial type transformer without using a stepup transformer?