plz tell me about for how many rating (for 500kva)how much
current taken?
Answer Posted / kapil
what is .8 doing in the above formula, while the rating is
given in the KVA and not in Kwatt.
the formula is ..KVA=1.732x Volt x Amp
where voltage will be taken as 415 volt. which is very
common in 3 phase motor rating.
this will produce the same answer as above [695 amps]
| Is This Answer Correct ? | 27 Yes | 12 No |