can we load Power capicitors on DG sets?
Answer Posted / jigar shah
Capacitor requirement arises to effective utilization of
the generated power (to reduce the losses mainly-cu losses
& line losses) & all switchgear component.In general
practice Capacitors are not connected on DG Set.As per my
understanding following are the main reasons for which it
is not recommendation to run capacitors on DG set :
1. During no load condition capacitor will try to increase
the voltage level of genrated voltage which can damage the
insulation of wdg & wdg may get burnt
2. With increase in PF we will not ge much advantage as the
cable losses are negligle.Load is in nearest proximity of
the Equipment.
3. Capacitors can be installed at load side
Is This Answer Correct ? | 22 Yes | 0 No |
Post New Answer View All Answers
What are the main parts of central chiller plant? Explain the function of each stage.
All the socket in a room become very hot, the Wall was also became very hot and the earth conductor also became live, what in your view might be the possible causes?
how can we phase identification in a distribution line,how we recognise that which phase is coming for a house hold connection.help me............
What is true sine wave or pure sine wave inverter?? Is it sine wave or step wave?? If it is step wave, waves with how much step is considered as pure sine wave? Is it possible to produce pure sinewave using power electronics?
How to design the NGR Resistance
What are the main faults of DC generators?
Who many reason of ignition fail ?
What is the rating of circuit breaker needed for 300 KVA load in 33 KV supply line in a transformer of 33 KV / 415 Volt ?
What is contract demand in solar system?
how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING) I O (current operating)?
what is the ground fault relay,which purpose it will be use,clearly tell me plz
how to differentiate a mpcb,mcb with a contactor? Explain their working operation
Can RCD's used to protect the VVVF drive if not why.
how to calculate regulation constants for over head lines? and what are the regulation constant for raccoon conductor at different voltage level and different P.F?
what are factors to be consider in electrical installation like load factor,diversity factor .....