Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how to calculate knee point voltage of current transformer?

Answer Posted / lakshmikanthan

V(kp) = 2 * IF(A) * (RCT(Ω) + RL(Ω) + RB(Ω)) / CT
If= fault current
Rct= resistance of CT winding secondary
Rl= lead resistance
Rb= relay resistance for measuring terminal
CT= ct ratio

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Why AC current leads voltage in capacitor and how?

2162


how to calculate the settings for shaft ct protn in hydro generators

1977


in wind mill use 2100 kw asychronous generator ( induction generator ) rotor voltage : 3300,stator voltage : 690, rpm : 1511 type : MRL063E04 ' we check rotor resistance magger value found following. R-EARTH - 00 M.OHM,Y-EARTH-34 M.OHM,B-EARTH- 33M.OHM R-Y: 31 M.OHM, Y-B: 00 M.OHM,B-R :33 M.OHM HOW CAN I TAKE DECISION?pls ans. quickly

2309


best manufacturer for busbar for outdoor switchyard having double bus bar scheme, can any one share technical specification of busbar. 132kv voltage ?

1727


why to use freewheeling diode ( diode in revers bias mode) across dc coil

5037


difference between main metering kiosk and check metering kiosk

3010


Why Stabilising Resistor used in REF circuit ?

3330


Explain thin film resistors and wire-wound resistors

1031


33kv substation lay out details & line to line & line to earth measurements

2625


how can get electrical c licence.now i am working in spining mill , transformer capacity 2750KVA. SANCTION DEMAND 2250KVA. PLEASE ADVISE ME . MY CONTACT NO 09944226823

1803


How PSV sizing being done

2337


how can you calculate fault level ?

2403


I want to replace the 3 KW DC motor with AC motor so what should be the rating of AC motor? Details Of DC motor to be changed with AC are - Kw - 3, Vf - 310, If - 0.15, Va - 400, Ia - 13, RPM - 2400

1819


what is sevice settings for mccb?How can be it setted?

2224


Which of the following alternatives will be cheaper (1) A 100 h.p AC, 3-phase motor (2) Four motors of 25 h.p each (3) Five motors of 20 h.p each (4) 10 motors of 10 h.p each explain

3037