Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Dear All,
Can anybody please tell me which value(saturated or unsaturated) of sub-transient reactance(Xd") we take for the calculation of fault current of the system?

Answer Posted / yegneswaran

Saturated machines will have lesser reactance compares to unsaturated ones...

Hence, fault current is more while saturated subtransient reactance taken into account...

We should consider saturated subtransient reactance while calculating fault current value.

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

A commercial Building is designed with 14th floor levels with indoor substation of three phase transformer with rated capacity of 1000 Kva.The transformer delivered 65% of its rated capacity at 0.67 power factor lagging.Because of low power factor, the power customer was penalized and certain cost was charged accordingly based on every point percentage lower than 85%.This situation may repeatedly happen on the succeding energy bills of power customer.The power customer is desired to improve its historical power factor of 0.67 lagging and no further penalty be impose by the local power company on the next bill. Q: Identify the appropriate solution you want to offer to Client?.Justify SCIENTIFICALLY and MATHEMATICALLY the principles behind the solution.

1777


Earth is a conductor or load?then ammeter connect to 3- phase supply,it shows the measurents or not?

2065


What are the three constants associated with a steady state error?

1209


how did the testing of protection relays done through current injection

2075


What happens to a motor if it is connected in Delta connection

1053


how to calculate sizing of NGTR (Transformer rating,Loading resistor value and Current rating of resistor) and what is the X/R ratio. Details : 11kV,Capacitance 1.73532 micro farads,40kA for 1sec.

2263


why 5kW motor becomes unbalance if its relay trip 1st time and its set value is 7.0 A

1995


A car's starter motor draws a current of 100 A at 12,0 V when starting the engine. The mechanical power required to turn the engine is 960 W. At what rate is energy from the battery converted to non-mechanical forms of energy?

2164


How to calculate cable rating for 3 phase supply?

2172


While testing LA mast,What are the parameter limits ?

1893


Dear friends, i would like to know that what is the exact function of 'exciter winding' & 'aux winding' in Alternator?

2004


Whata are the types of Cables?

2141


How can we checked Killo Watts of Motor & Alternator?

2145


when ID fan will immediately stop through VFD what exactly cause and problem the ID fan

1444


XYZ

2133