How does frequency affect KVA rating of a transformer?
If a 500 kva, 400 v, 60 hz t/f is to be operated on 50 hz
frequency then how will its KVA rating change?
a-increase
b-decrease
c-remains same
Also explain why do u think like that.
Answer Posted / jinboll
The transformer EMF equation shows that the EMF induced in the secondary or the primary side of a transformer is directly proportional to the product of the flux (Φm) through the transformer core and the frequency. This leads to the flux is proportional to E/f.
For example, the kVA rating of the 500v to 250v 60 Hz transformer will be smaller when used in Europe with a frequency of 50Hz. 500/60 = E/50, E is smaller than 500v on primary side. 250/60 = E/50, E is smaller than 250v on secondary side.
| Is This Answer Correct ? | 10 Yes | 2 No |
Post New Answer View All Answers
(In MEP services) HVAC in AC Plant room what else can we provide if the chiller is not considered?
what is the maximum temperature rating of a thhn insulated conductor?
How to know the following data of synchronous generator 1. D-Axis Unsaturated Reactance 2. D-Axis Unsaturated Transient Reactance 3. D-Axis Unsaturated Sub - Transient Reactance
why are installed water leakage detection system data centers & server rooms
how to select the mpcbs and contactor for 3 phase 30 hp star delta motors.for plc control.and tell me the calaculation for future use.
What is tan delta & PPM in transformer? and whats its IS value?
If you don’t have coal, salt and copper, then how would you earth your connection temporarily at a camp site.?
1 hp is equal to how much watt?
Explain Creepage Distance of Insulator
Why transformer used in UPS??
apti mainly on logical reasoning, verbal and non-verbal ability (70 percent) and remaining technical. I was in ee but technical had mech ques like on turbines and welding.
The size and construction of bushings in a transformer depend upon?
iam using DM 3251 voltmeter(1 percent accuracy)for 11KV system PT ratio is 11KV/110V.can anybody explain what is the max and min voltage deviation.
I have a situation to design sub-Distribution board/Panel meant for feeding power sockets. In the incomer CAN i Take TP MCCB with Neutral Link and All the outgoing feeders with to sockets with TP MCCB and Neutral Link? P.S : My System is IT Earthing
Can clean earth cable be considered as low current cable